4.3.7 Manual control panel setup
Manual control panel setup is completely different from other linkages. It connects a direct
control button with a module in the loop. The integrated meaning is: direct control button
corresponds to a module selected completely controls the start/stop of the module listed in the
result list.
The corresponding relation between control button and module is one-to-one, so only one
module address can be added in the result list of manual control panel setup.
Fig 4- 44 Manual control panel setup
The settings above can be explained:
4.3.8 Broadcast control panel setup
The setup window shows below:
Fig 4- 45
Broadcasting panel setup
The broadcasting panel is a brought-in product which can be connected to our host through
485 port. The maximum capacity is 90 controllable points.
Once registered on the host, it can communicate with the host and the number of
controllable points can be configured among 30, 60 and 90.
4.3.9 Broadcasting point setup
The setup is similar to setup for manual control panel. The function is independent of the
fire alarm control panel manually controlling the corresponding broadcast module. The
broadcast controlling button selected will sheerly start/stop the module chosen on the output list.
Note: register the broadcast panel before using this function.
The Button 1 on the manual control panel of Loop 1of IO-board 1 controls the no.238
module on Loop 1 of IO-board 2 of Host 2.