Fig 4- 46 Broadcast control panel - manual point setup window
4.3.10 Fire hydrant setup
The four/six-wire fire hydrant produced by our company can be used as four-wire fire
hydrant and is compatible with the functions of old six-wire fire hydrant. When used as four-wire
fire hydrant, the corresponding relation between water pump shall be set by the setting function.
The goal is to reduce the difficulty of actual installation and debugging of six-wire fire hydrant.
Thick linkage means:
When the water pump selected at the condition setting column
starts or stops and "all fire hydrants" are chosen as the output result, then all fire
hydrants in the loop will have the corresponding optical signal indication. Otherwise, the
fire hydrants displayed at the output result list will have the corresponding optical signal
indication.
Note:
The corresponding fire hydrants only will generate optical signal indication with this
function, and thus they will not displayed at the alarm interface and the historical information.
The corresponding relation of this type shall be provided with at least one output result,
therefore at least one data shall be added in the output result list as the result, even though all
fire hydrants have been selected as the output result.
Fig 4- 47 Fire hydrant - fire pump correlation setup