Fig 4- 39 Building linkage setup
The drop-lists of zone, building, floor range are added. The equation above represents the
following:
4.3.4 Floor linkage setup
The floor-related linkage conditions in the system include two types: type output and point
input.
The figure below presents the floor linkage setup of type output, floor options are
unavailable in the condition setup, a check box "scroll" is added only and a certain or some
equipment types can be selected in the optional module list.
The floor linkage linkage of type output means: when detector or module of any specified
type at any floor gives an alarm, the equipment of a certain type or some types at the floor will
carry out actions completely. If "scroll" is selected, the equipment of same type at adjacent floors
will carry out actions in the meantime.
Condition
Result
In building 1 of zone 1:
When the following happens at floor -1
to 23:
Any one of smoke valves activated
The
smoke
exhaust
fan
connected to the No.5 module
in loop 1 of IO-board 1 will start
without time delay.