Chapter 6 Instruction of Manual Control Panel
Several manual control panels (also known as Fireman Panel) can be included in the system
for customer to directly take the control of equipment manually. Each panel (2U panel) includes 30
manual points with 2 LEDs per point: one LED for request to start and one LED for feedback signal
from the equipment.
Fig 6- 1 Manual control panel
Each manual point will take up an address, thus each panel will take up 30 addresses in
sequence. The panel number that can be included depends on how many IO-boards in the system.
There are 11 choices as the starting address: 1, 31, 61, 91, 121, 151, 181, 211, 241, 271 and 301.
The address setup can be achieved through the four jumpers of JP1, JP2, JP3 and JP4 on the
circuit. See the table below for reference.
Fig 6- 2 Detail diagram (10 points)
Note: the panel is designed with 30 points, thus
30 more points will be added every time to
extend the manual points.
Fig 6- 3 Address setting diagram
More details please check the separate manual for the ZX900-10A panel.