Adding a linkage condition: click on Add button
Deleting a linkage condition: click on Del button
Viewing or editing the linkage condition on the previous page: click on Prev
Viewing or editing the linkage condition on the next page: click on Next
Viewing or editing a certain linkage condition: enter serial number of the linkage condition
into the text box before "Pg", enter or click on to.
The system will display another linkage condition when any of the above operations is
carried out. "Cond. 1/3" at top left corner of the display means currently there are 3 system
linkage conditions and the first one is displayed at the moment. If the linkage conditions are
large in number, enter into the page number to skip. If the corresponding modules of a linkage
condition are multiple, the page switching may take 2-5s.
The edit area for current linkage condition is set below the condition setting area.
"Delay": select the time interval between condition satisfied and action of module;
"Reg": check the option to activate the linkage action on this page;
"Input type": composed of check box at the left side and drop-down box at the right side. The
relation between input type is "or";
"Fire QTY": the number of fires required to satisfy a condition. For example, 01 means the
conditions are satisfied when the alarms is generated at any 1 point. The system can achieve
composite functions of multiple arbitrary alarms and the maximum composite number is 99.
Therefore, the linkage conditions in the above figure are as follows
Step 2: Select the number of IO-Board and the number of Loop
When the target IO-Board and Loop are chosen, the output devices available will be listed
to choose from.
Step 3: Select the module required to be started when conditions are satisfied
Click on a certain module in the list box and click on << button, to add this module into the
result list area. Except for "manual control panel linkage setup", a linkage condition can be used
to start multiple modules, therefore step 2 and step 3 can be repeated to add multiple output
results.
The modules started by a condition are limited in number and a condition can be used to
start 200 modules at most. If the number exceeds 200, the user must set another different
number with the same conditions, to correspond to modules with numbers exceeding 200.
Check a module in the "Result list" and click on >> button to delete the module from the
result list.
The display of result output column in the figure is as follows:
If it is indicated that the linkage condition is true, two modules (module 1 and module 2) will
be requested for action. The two modules control fire pumps.
Note:
In the linkage interface, only the module address number can be selected, the equipment
controlled by the module shall be set at the detector/module setup form.
Step 4: Confirm
Press Confirm button and the system will save the linkage condition and exit the linkage
setup interface. Press Add, Next or Prev to switch to another linkage condition setup interface to
proceed. At switching over, the system will save the linkage conditions set just now.
The setup of a linage relation is completed after conducting the above 4 steps. The
following section will present respective diagrams.