45
An actuator fitted with the interrupter
timer and set as the example shown in
these instructions would operate at:
Rated speed from full Open to
25% Open.
1
/
6
rated speed from 25% Open to Fully
Closed and from Fully Closed to 25%
Open.
Rated speed from 25% Open to Fully
Open.
WARNING: The interrupter
timer does not operate during
mains power failure on spring
return actuators. Systems should
take this into account.
Example
The interrupter timer may be overridden
when the actuator is under software
ESD signal command. This will mean
the actuator will run to limit without
“stop/start” action under ESD
command.
Refer to section 9.5 for ESD settings.
The default for ESD override interrupter
timer is
[OF]
No
. The interrupter timer
will continue “stop/start” action during
software ESD action.
If ESD must override the timer use the
+
or
-
to display
[O
n
]
Yes
.
PRESS THE
KEY.
The displayed option will flash (stored)
indicating that it has been set.
Timer Override
ESD:
Off
JE
ESD Override
Interrupter Timer