Commissioning – Basic Functions
continued
Each actuator is built in the factory to
be either Normally Closed, Normally
Open or Stay-put depending on what
configuration was ordered.
Normally Closed:
Quarter-turn
(spring-return clockwise)
Linear
(spring-return to extend)
Normally Open:
Quarter-turn
(spring-return anti-clockwise)
Linear
(spring-return to retract)
Consult factory if this configuration
needs to be changed as it cannot be
done through software alone.
The actuator can be configured to
either close on Pressure (hydraulic or
spring) for seating valves or Limit for
non-seating valves.
50
m
50
m
P?
k
PC
k
bt
k
Pt
k
Ft
m
Cr
m
C2
k
C3
m
CP
k
cP
k
OP
k
oP
m
LC
k
LO
m
50
Refer to valve manufacturer for
recommended setting.
[CP]
Stop on Pressure (Default)
[CL]
Stop on Limit
To change the function press the
+
or
-
key until the required setting is
displayed.
PRESS THE
KEY
.
The displayed option will flash (stored),
indicating that it has been set.
Close Action
C2
Close Action
Stop on Pressure
Torque