32
Closed LED
Colour
It is possible to use an external power
supply such as a solar power system
for 24 VDC actuators. If this is the
case then it is beneficial to limit power
consumption while the actuator is at
rest.
There are three options available to
configure the power consumption:
[OF]
Off (Default):
Select this option
to turn the display backlight on
permanently.
[On]
On:
Select this option to
automatically switch the display
backlight off. This will be done 5
minutes after the actuator was last
used with either the setting tool or local
controls.
[EL]
Extra:
Select this option to further
reduce the power consumption
by inverting the monitor relay and
disabling the CPT output.
To change the configuration press the
+
or
-
key until the required setting is
displayed.
PRESS THE
KEY.
The displayed option will flash (stored)
indicating that it has been set.
Low Power Mode
LP
Low Power Mode
Off
There are two options available:
[gr]
Green (Default):
Select this option
for the LED to be green at the closed
limit and red at the open limit.
[RE]
Red:
Select this option for the LED
to be red at the closed limit and green
at the open limit.
To change the configuration press the
+
or
-
key until the required setting is
displayed.
PRESS THE
KEY.
The displayed option will flash (stored)
indicating that it has been set.
Ld
Closed LED
Colour:
Green
There are two options available to
configure the operation of the local
controls:
[Pr]
Push to Run (Default):
Select this
option if the actuator is required to stop
when the knob is released.
[nn]
Maintain:
Select this option if the
actuator is required to run to either the
open or closed limit when the knob is
released.
To change the configuration press the
+
or
-
key until the required setting is
displayed.
PRESS THE
KEY.
The displayed option will flash (stored)
indicating that it has been set.
Local Control
cL
Local Control
Push to Run