44
Interrupter Timer
Off Time
Interrupter Timer
On Time
Using the
+
or
-
key select the position
for the
TIMER TO STOP WHEN THE
VALVE IS OPENING.
[
] [
]
Closed
= valve closed
[00]
to
[99]
= percentage open
[
]
Open
= valve open
PRESS THE
KEY.
The displayed option will flash (stored)
indicating that it has been set.
If timing is not required in the opening
stroke select
[JO]
to
[
] [
]
.
Using the
+
or
-
key select the
actuator run period in the range 100
mS to 99 seconds.
[Jn]
set to 05 gives an Interrupter
Timer on pulse length of 500 mS or 5
seconds depending on whether
[JS]
is
set to
[OF]
or
[On]
.
PRESS THE
KEY.
The displayed option will flash (stored)
indicating that it has been set.
Using the
+
or
-
key select the
actuator stop period in the range 100
mS to 99 seconds.
[JF]
set to 25 gives an Interrupter Timer
off pulse length of 2500 mS or 25
seconds depending on whether
[JS]
is
set to
[OF]
or
[On]
.
PRESS THE
KEY.
The displayed option will flash (stored)
indicating that it has been set.
Timer Stop
Position:
25%
Timer On Time
05 Seconds
Timer Off Time
25 Seconds
JO
Position in Valve Opening
Stroke for Timer to Stop
Jn
This function changes the units of
time applied to
[Jn]
and
[JF]
between
seconds and milliseconds.
[On]
Seconds (Default)
[OF]
Milliseconds
To change the time interval press the
+
or
-
key until the required setting is
displayed.
PRESS THE
KEY.
The displayed option will flash (stored)
indicating that it has been set.
Timer Interval
Seconds
JS
Interrupter Timer Interval