36
ESD Contact Type
Normally Open
ESD Contact Type
Ec
This setting determines if a signal
should be applied, or removed to
initiate the software ESD action.
[nO] Normally Open (Default):
The
ESD signal has to be applied to perform
software ESD function.
[nC] Normally Closed:
The ESD signal
has to be removed to perform software
ESD function.
To change the ESD Contact press the
+
or
-
key until the required setting is
displayed.
PRESS THE
KEY.
The displayed option will flash (stored)
indicating that it has been set.
ESD Manual Reset
No Reset
ESD Manual Reset
This feature allows the actuator to be
disabled from operational commands
after an ESD event until it has been
manually reset. To perform a manual
reset the red local controls knob has to
be moved to Stop and then to either
Local or Remote. Once this is done the
actuator can be commanded to move
again.
This works in both Hardware and
Software ESD.
[OF] No Reset (Default):
Select this
option if the actuator does not need
to be reset after a ESD event or loss of
mains power.
[Ed]
After ESD:
Select this option if the
actuator must be manually reset after
an ESD event.
[LP] After Mains Loss:
Select this
option if the actuator must be manually
reset after loss of mains power.
[On]
ESD/Mains Loss:
Select this option
if the actuator must be manually reset
after an ESD event or loss of mains
power
To change the Manual Reset option
press the
+
or
-
key until the required
setting is displayed.
PRESS THE
KEY.
The displayed option will flash (stored)
indicating that it has been set.
rE
ESD Override
Local Stop:
No
ESD Override
Local Stop
EO
The feature allows you to choose if an
active ESD signal should override Local
Stop.
[OF] No (Default):
Select this option if
a software ESD command should NOT
override Local Stop.
[On]
Yes:
Select this option if a
software ESD command should override
Local Stop.
To change the setting press the
+
or
-
key until the required setting is
displayed.
PRESS THE
KEY.
The displayed option will flash (stored)
indicating that it has been set.