19
7
Commissioning
continued
7.12 Crossroad [Cr]
To access the Basic Settings
press the
arrow
m
key
.
Refer to 8.
To access the Configuration Settings
press the
arrow
k
key
.
Refer to
Section 9.
7.13 The Actuator Display –
Setting/Checking Mode
Actuator functions as laid out in the
Basic and Configuration commissioning
stages, can be individually displayed by
using the Setting Tool arrow keys.
The
m
arrow key will always display the
FIRST function on the next level DOWN
within the procedure.
The
k
arrow key will always display
the NEXT function on the SAME level
and will wrap around the functions on
the same level.
Actuator functions are displayed in code
form in the top left portion of the liquid
crystal display screen.
The setting for the displayed function is
shown in the top right hand portion of
the screen. Depending on the actuator
function displayed, its setting may be
an option or a value.
Text relating to the function and setting
values will be displayed in the lower
display.
7.11 Full Stroke Test
This function performs a full stroke test
based on a setup test being completed
in
[SF]
. Insight II can then be used to
compare subsequent full stroke tests
against the original test when the
actuator was first commissioned.
The actuator must be in Local to
perform a test.
The actuator needs to be moved to
either the closed or open limit prior to
initiating the test.
[Ft]
Perform the partial stroke test.
PRESS THE
KEY.
This brings up an option to either
cancel or confirm that the full stroke
test should be completed.
To cancel the test: Ensure that
[No]
is
displayed on the screen.
PRESS THE
KEY.
To confirm that the test should be
completed: Press the + key until the
display changes to
[yS]
PRESS THE
KEY.
Confirm?
Full Stroke Test
- No +
Full Stroke Test
- Yes +
Full Stroke Test
Basic Setup
Config Setup