30
Indication Contact r1
Indication contact r1 may be set to trip
for any one of the following functions:
Code Function
(as displayed)
[CL]
Closed Limit
[OP]
Open Limit
[FA]
Fault Alarm
[Po]
Position % Open
[rr]
Motor Running
[dC]
Closing
[dO]
Opening
[rn]
Moving
[St]
Stall (mid-travel)
[SE]
Stall (end of travel)
[SP]
Stall (any position)
[Pt]
Over pressure (mid-travel)
[PE]
Over pressure (end of travel)
[PP]
Over pressure (any position)
[LS]
Stop Selected
[Lo]
Local Selected
[rE]
Remote Selected
[CA]
Control Alarm
[ES]
ESD Active
[tt]
Temperature (°C)
[HA]
Manual override switch
[AS]
Accumulator pressure switch
[Er]
External manual reset switch
[Ht]
Motor thermostat switch
[PP]
Partial stroke passed
[PF]
Partial stroke failed
[n2]
Monitor 2
[OF]
Off
The r contact form can be set normally
open
[nO]
or normally closed
[nC]
.
Unless specified with order, the
default setting for indication
contact is the following:
r1 – [CL] Closed Limit [nO]
9.2
This screen will only be displayed if the
relay function is set to
[Po]
Position %
Open and
[tt]
Temperature (°C).
When the relay function is set to either
[Po]
or
[tt]
, the required trip value
must be set.
The value can be set from 1% to 99%
in 1% increments for
[Po]
or 60 °C to
99 °C in 1 °C increments for
[tt]
.
To change the value press the
+
or
-
key until the required setting is
displayed.
PRESS THE
KEY.
The displayed value will flash (stored)
indicating that it has been set.
Relay 1 Value
r1
Relay 1 Value
Position: 25%
To change the function press the
+
or
-
key until the required setting is
displayed.
PRESS THE
KEY.
The displayed function will flash
indicating that it has been set.
Relay 1 Function
r1
Relay 1 Function
Closed Limit