18
7
Commissioning
continued
7.9 Bluetooth Diagnostic and
Configuration
EH
Pro
actuators include a
Bluetooth
interface as standard, allowing non-
intrusive diagnostics, analysis and
configuration.
Insight II software for PC has been
developed to enable the actuator
configuration and onboard Datalogger
to be reconfigured and analysed. A PC
running Insight II software can be used
to interrogate the actuator via non-
intrusive
Bluetooth
communication. Visit
www.rotork.com for information.
Alternatively, the intrinsically safe Rotork
Bluetooth
®
Setting Tool
Pro
allows the
user to extract and store EH actuator
configuration and Datalogger files
within the tool. Stored files can then be
uploaded via
Bluetooth
to a PC running
Insight II where they can be viewed,
analysed and stored in a safe, clean
environment.
Using the Rotork
Bluetooth
®
Setting
Tool
Pro
, actuator setup can be
configured on the PC, stored in the
tool, transported to the actuator
and uploaded. The tool can transfer
the same configuration to multiple
actuators where actuator setup is the
same.
Refer to PUB095-001-00 for full
instructions on the use of the Rotork
Bluetooth
®
Setting Tool Pro.
To enable communication with Insight
II, the actuators
Bluetooth
interface
must be enabled.
The default setting for the
Bluetooth
interface is
[OF]
disabling
Bluetooth
.
[OF]
Off (Default):
Bluetooth
is disabled
[ON]
On:
Bluetooth
is permanently
enabled.
[LS]
Local Stop Only:
Bluetooth
is only
enabled when the actuator is in Local
Stop.
To change this setting press the
+
or
–
key until the required setting is
displayed.
PRESS THE
KEY.
The displayed option will flash (stored)
indicating that it has been set.
Off
Bluetooth Comms
7.10 Partial Stroke Test
This function performs a partial stroke
test based on the parameters set in
[PP]
and a setup test being completed
in
[SP]
. Insight II can then be used to
compare subsequent partial stroke
tests against the original test when the
actuator was first commissioned.
The actuator must be in Local to
perform a test.
The actuator needs to be moved to the
correct limit prior to initiating the test
[Pt]
Perform the partial stroke test.
PRESS THE
KEY.
This brings up an option to either
cancel or confirm that the partial stroke
test should be completed.
To cancel the test: Ensure that
[No]
is
displayed on the screen.
PRESS THE
KEY.
To confirm that the test should be
completed: Press the + key until the
display changes to
[Ys]
PRESS THE
KEY.
Confirm?
P-Stroke Test
- No +
P-Stroke Test
- Yes +
P-Stroke Test