Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
Operation
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
101
8.3
Zero adjust (after sensor exchange)
1 Push
the
MENU
key, switch to "change" with the
key and confirm with the
ENTER
key
2
Enter the password (if active)
3
Switch to "System adjustment" and confirm with
ENTER
key
4
Select the desired program number at the control unit
5
Switch to adjustment parameter “Zero adjust”
6
Select "zero adjust" and confirm with
ENTER
key
7
The message "remove sheet" appears, perform this and then confirm with
ENTER
key
8
After the message "zero adjust active“ the message "zero adjust completed" is shown.
Then
confirm
with
ENTER
key
9
Return into the measurement mode with the
MENU
key
8.4 Teach-In
1 Push the
MENU
key, switch to "change" with the
key and confirm with the
ENTER
key
2 Enter the password (if active)
3 Switch to "Program parameter" and confirm with
ENTER
key
4 Select the desired program number at the control unit
5 Switch to “Teach-In” (1-sheet or 2-sheet / Part A or Part B)
6 Select "Teach-In statical" or "Teach-In dynamical" and confirm with
ENTER
key
7 Feed (pan through) a sheet and then confirm with
ENTER
key
8 Return to the measurement mode with the
MENU
key
The exact Teach-In procedure is described in the chapter “Program parameters” – “Teach-In".