Manual
Double Sheet Detector-series I20
Start-up
B0069991 / Rev. 1.7
68
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
6.3.12 Reset error
With the “Reset error” function uncritical faults can be redressed.
Critical errors like “cable rupture” can only be redressed with the control unit keys.
1
Before the “Reset error” is initiated, all inputs must be LOW for 10 ms.
2
Switch input IN9 “Reset error” to HIGH.
3
Within 10ms all outputs are switched to LOW.
If the fault can be reset, the output OUT0 will be set to HIGH.
4
Switch the input IN9 “Reset error” to LOW.
5
Within 10ms all outputs are switched to HIGH.
6.4
Internal control (Demo mode)
In this operating mode the system continuously executes measurements and activates
OUT0 … OUT4.
In general, this operating mode is suitable for demonstration purposes only.
Prerequisites:
•
Supply voltage applied
•
System parameter “Measurement mode” set to “demo”
•
Teach-In has been executed