Section 22.
SIMPLIFIED COMMISSIONING PROCEDURE
And FUNCTIONAL TEST PROCEDURE
22.1
SIMPLIFIED COMMISSIONING PROCEDURE
1) Check the carrier output level by removing the coax from carrier output to the line tuner.
a) Connect a 50-ohm non-inductive dummy load of sufficient wattage to the carrier output
connector. Place the Frequency Selective Volt Meter (FSVM) leads on the Output Filter TP1
(Brown – “COM”) and TP3 (White – “IN”), check for the following level:
2) 10W applications measure 22.36 Vrms (40dbm)
TP1/COM
Brown
TP3/IN
White
RFL 9785
RFL Electronics Inc
.
Figure 22-1. Controls and Indicators, 9785 Output Filter Modules
(106530-1 to -5 WITHOUT RPM Option)
J1
Note: Only for step
Error! Reference
source not found.
of
Transmitter
Functional Test
TP1
(COM)
Brown
TP3 (IN)
White
Figure 22-2. Controls and Indicators, 9785 Output Filter Modules
(106530-11 to -15 WITH RPM Option)
March 1, 2013
22-1
(973) 334-3100