Room temperature settings
(Only with a room unit or sensor installed)
Room temperatures for time program 3.3 can be set in menus:
5.1.19.2. Room Reference (Day)
The desired room temperature for day mode.
5.1.19.3. Room Reference (Night)
The desired room temperature for night mode.
5.1.15. Room hysteresis
Hysteresis for switching on the heating circuit again when the room temperature drops.
Switching from the Summer mode is controlled by the outdoor temperature.
This can be set only when “ room” is selected in menu 5.1.14.
5.1.19.1. Room Controller
This value is used to appoint the amount of influence the room temperature has on the
reference flow temperature, as a percentage. With higher percentage, the flow temperature
is more influenced by the indoor temperature which limits overheating or underheating of a
building. Lower percentage is suitable for a reference room that is more exposed to sunshine
or fitted with a fireplace – other rooms in the building could suffer from underheating.
Flow temperature correction is possible only within the limits of the Min. (5.1.9.) and Max.
(5.1.10.) Flow temperature.
Temporary comfort boost
A special time program to boost the flow temperature. It can be used e.g. for a faster transition
from the night to the day temperature.
3.4. Heating Circuit Comfort (time program)
Setting time periods for each day with a higher flow temperature.
The temperature increase can be set in menu 5.1.8.
5.1.8. Comfort boost
The value of further flow temperature increase, independent of other time programs.