34
E.4. GENERAL SETTINGS
3.1. Time & Date
In the event of a power failure, check the time on the controller. If the power failure lasts more
than 24 hours, the clock in the controller will stop.
3.2. Daylight saving time
Setting of an automatic change to and from DST.
4. Operating Mode of the Controller
Leave the automatic mode here. Manual mode is for service purposes only.
6.1. Seizing Protection
If the anti-seizing protection is activated, the controller switches gradually all outputs at 12:00
noon for 5 seconds to prevent seizing of the pump/valve after long periods of inactivity.
7.12. Commissioning
This will launch the setup wizard.
7.13. Factory Settings
After resetting to the factory settings, it is advisable to launch the setup wizard.
8.1. Menu Locku
Securing the controller against unintentional changing the set values. Unlock by simple
switching off this function.
10. Language
This is used to select the language for the menu guidance. The following languages can be
set: German, English, French, Italian, Spanish, Czech, Polish, Russian or Dutch..
E.5. ADJUSTING TEMPERATURES & TIME PROGRAMS
Heating water settings
3.3. Heating Circuit (time program)
This menu is used to set the Day (comfort) and Night (setback) mode times for the heating
circuit. The factory set time period for Night mode is from 22:00 to 6:00.
Note: increasing (decreasing) the heating water temperature by 3 °C in systems with radiators
will usually result in a room temperature increase (drop) by 1 °C approx.
Heating water temperatures for time program in 3.3. can be set in menu:
5.1.6. Day Correction
The value by which the heating water flow temperature is increased.
5.1.7. Night Correction
The value by which the heating water flow temperature is decreased.
If you do not wish to use the time program, set the corrections in 5.1.6. and 5.1.7. to 0.