22
D.2. ROOM TEMPERATURE SENSOR
Description
The room temperature sensor allows for more precise control of
the room temperature.
It shall be ordered separately, code 16167, and it is an alternative
to the Caleon room unit.
Intended for variants
1 (options A, B, C)
Installation
It shall be installed on a wall in a reference room at a height
of 1.2 to 1.6 m above the floor, out of direct sunlight and far
enough away from the windows. It must not be installed near
heat sources.
Settings in controller
After connecting the room sensor, no further controller settings
are needed, just select the desired room temperatures in menu
5.1.19.2 and 5.1.19.3 and, if necessary, the time program in
menu 3.3.
Connecting terminal
S1
El. wiring
permissible conductor cross section – 0.5-1.5 mm
2
! Max. permitted cable length for the Pt 1000 room temperature
sensor is 10 m!
Wiring diagram
POWER SUPPLY
EXTRA LOW VOLTAGE
located on the top cover of the printed circuit board