Installation and Wiring
4-7
PL B900/B910 Series Users Manual
(a) Dedicated Ground - best *1
• Set up a dedicated ground when using
the rear panel’s FG terminal.
(b) Shared Ground - allowed *1
• If a dedicated ground is not possible,
use a shared ground, as shown in fig-
ure (b).
• The grounding point must be as close
to the PL as possible, and the ground-
ing wires must be as short as pos-
sible. If the wires must be long, use
thick, insulated wires and run them
through conduits.
(c) Shared ground - not allowed
PL
PL
Other
device
Other
device
Other
device
PL
*1
Use a grounding resistance of less than 100
Ω
and a 2mm
2
or thicker wire, or your
country’s applicable standard. For details, contact your local PL distributor.
.
4.3.3 Grounding Cautions
4.3.4 Cautions When Connecting I/O Signal Lines
• I/O signal lines must be wired separately from charged lines. If the power cord
needs to be wired together with the (I/O) signal lines for any reason, use
shielded lines and ground one end of the shield to the PL’s FG terminal.
• To improve noise immunity, attaching a ferrite core to the power cord is recom-
mended.
Summary of Contents for PL-B900 Series
Page 12: ...12 PL B900 B910 Series Users Manual Memo...
Page 38: ...Chapter 2 Specifications 2 18 PL B900 B910 Series Users Manual Memo...
Page 62: ...Installation and Wiring 4 8 PL B900 B910 Series Users Manual Memo...
Page 80: ...System Setup 5 18 PL B900 B910 Series Users Manual Memo...
Page 84: ...PL B900 B910 Series Users Manual 6 4 Memo...
Page 88: ...7 4 PL B900 B910 Series Users Manual Memo...
Page 98: ...Appendices App 10 PL B900 B910 Series Users Manual Memo...