Pressure Systems, Inc. Model 9116 User’s Manual
Page 84
www.PressureSystems.com
ii
dd
Description
‘q’ read
index
0C
00
01
Set Cal Valves to RUN or LEAK Position
(default)
— choice made by
ii
=12.
Set Cal Valves to CAL/RE-ZERO or PURGE Position
—
choice made by
ii
=12.
0B
see chart
below
0D-0E
--
Reserved for factory use
0F
00
01
Disable periodic
Thermal Coefficient Update
task.
Enable periodic
Thermal Coefficient Update
task (default).
10
01-20 Set
Number of A/D Samples to Average
,
(default = 8).
Valid values are 4, 8,16, 32, and 64. Other values below 64
are rounded up to the next valid value listed above.
05
11
--
Reserved for factory use
12
00
01
Set Cal Valves to RUN or CAL/RE-ZERO Position
(default)
— choice made by
ii
=0C.
Set Cal Valves to PURGE or LEAK Position
— choice made
by
ii
=0C.
0B
see chart
below
13
00
01
Use
Static IP Address Resolution
(default)
Use
Dynamic IP Address Resolution
(
RARP/BOOTP)
(Results in immediately becoming the module’s new power-on
default)
06
14
00
01
02
Disable
Host Response/Stream Back-Off Delay
(default).
Enable
Host Response/Stream Back-Off Delay
as low-order
byte of Ethernet Address(converted to decimal value * 20
sec.).
Enable
Host Response/Stream Back-Off Delay
specified
per
eeee
as decimal value (* 20 sec.)
07
16
00
01
Disable
Host Response/Stream Total Size Prefix
(default).
Enable
Host Response/Stream Total Size Prefix
(2-byte
big-endian binary value with total size of response or stream
data in bytes that follows it).
08
17
00 Set
TCP Connect Port
per
eeee
as decimal value
(default=9000).
09
18
00
01
Disable
Auto UDP Broadcast at Reset
(default).
Enable
Auto UDP Broadcast at Reset
.
0A
19
00
01
Set
Minimum Temperature Alarm Set Point
(in
N
C)
per
eeee
as decimal value (default = 0
N
C).
Set
Maximum Temperature Alarm Set Point
( in
N
C)
per
eeee
as decimal value (default = 60
N
C).
0D
0E
1B
00 Set
Thermal Update Scan Interval
per
eeee
as decimal
value (seconds), 1 <=
eeee
<= 3600 seconds (default = 15).
11