ICE1-*-G60L-V1D, ICE1-*-G60L-C1-V1D
Commissioning for EtherCAT
Content of Output Channel X5A
…
X8B
The values refer to the following:
•
X5A ... X8A: Output data channel A (contact pin 4) of outputs X5 to X8.
•
X5B ... X5B: Output data channel B (contact pin 2) of outputs X5 to X8.
PDO 0x1601, Output Data in Bit Format
7.2.5
Device Parameters
The modules support different parameters. The parameters are sent to the module during com-
missioning of the controller.
The following parameters can be set:
Possible Parameter Options for the General Module Settings
Index
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0x6200:0
1
X8B
X8A
X7B
X7A
X6B
X6A
X5B
X5A
Table 7.43
PDO
Content
Index
Size
Index
Size
Type
Name
0x1601
2
0x6220:01
0.1
BIT
Output channel X5A
0x6220:02
0.1
BIT
Output channel X5B
0x6220:03
0.1
BIT
Output channel X6A
0x6220:04
0.1
BIT
Output channel X6B
0x6220:05
0.1
BIT
Output channel X7A
0x6220:06
0.1
BIT
Output channel X7B
0x6220:07
0.1
BIT
Output channel X8A
0x6220:08
0.1
BIT
Output channel X8B
Table 7.44
Index
(byte)
Parameter
Default
Available in module vari-
ant
0x2300:01 Web interface locked: 0 = false, 1 = true 0
All module variants
0x2300:02 Force Mode locked: 0 = false, 1 = true
1
All module variants
0x2300:03 Disable all emergency messages: 0 =
false, 1 = true
0
All module variants
0x2300:04 Disable UL emergency messages: 0 =
false, 1 = true
0
Module variants with out-
puts such as 16DO,
8DI/8DO, 16DIO
0x2300:05 Disable actuator emergency messages
without U
L
: 0 = false, 1 = true
0
Module variants with out-
puts such as 16DO,
8DI/8DO, 16DIO
0x2300:06 DCU Start: 0 = locked, 1 = disabled, 2 =
run
1
Module variants with
decentralized control func-
tion (DCU)
0x2300:07 Automatic restart of output after error: 0
= false, 1 = true
1
Only 16DIO module vari-
ants
Table 7.45