ICE1-*-G60L-V1D, ICE1-*-G60L-C1-V1D
Commissioning for EtherNet/IP
Figure 5.6
12.
Configure the EtherNet/IP module and download the parameters to the controller.
Initial Settings for Connection Parameters
Configuration tools from other controller manufacturers may require additional parameters to
be entered to establish a communication connection between your EtherNet/IP I/O scanner
and the Ethernet IO modules. In such cases, the table below provides a list of useful parame-
ters:
ICE1-16DIO-G60L-V1D/ICE1-16DIO-G60L-C1-V1D with 16DI/DO Profile and Diagnosis
Transport type
Exclusive owner
Trigger mode
Cyclic
Requested packet interval (RPI)
Minimum 1 ms
Sender to target device (O>T) connection parameters
Real-time transfer format
32 bit Run/Idle header
Connection type
POINT2POINT
Assembly instance ID
100
Data type
USINT
Data size
1 byte
Data length
2 byte
Target device to sender (T>O) connection parameters
Real-time transfer format
Pure, non-modal data connection
Connection type
MULTICAST
Assembly instance ID
101
Data type
USINT