ICE1-*-G60L-V1D, ICE1-*-G60L-C1-V1D
Commissioning for PROFINET
2
0
1
9
-1
0
59
•
All other devices must be configured as redundancy clients.
•
Prioritized start-up (FSU) is not permitted.
•
The watchdog time for all devices must be greater than the reconfiguration time (typically
200 ms, min. 90 ms for ICE1-* modules).
•
We recommend using the automatic network setting on all devices.
The following images show a potential MRP ring configuration. The PLC is used as a redun-
dancy manager and all other devices are used as clients. We recommend activating the diag-
nosis alarms to detect individual failures.
1.
Select "Device View" (1) and the desired module in slot 0 (2).
2.
Then, in the "General" tab, select the "Advanced Options -> Media Redundancy" (3). Set the
"Media Redundancy Role" option to "Client" (4).
Figure 6.19
3.
Check the "Watchdog Time.
”
To do so, select the "Real-Time Settings" area in this module.
4.
Re-set the "Watchdog Time" if necessary (to at least 90 ms, usually 200 ms).
1
2
3
4