Even-Number DI/DO-Byte Profiles
ICE1-16DIO-G60L-C1-V1D (DCU Function)
Ethernet IO module with 16 digital inputs/outputs (16DIO), freely configurable and decentral-
ized control function (DCU function).
16-DI/DO DCU Profiles
8-DI/DO DCU Profiles
Generic 16 DI
Listen only
No
Output: 192
0 byte
Input: 102
3 byte
Generic 8 DI + DIA
Listen only
Yes
Output: 192
0 byte
Input: 104
6 byte
Generic 8 DI
Listen only
No
Output: 192
0 byte
Input: 105
2 byte
Table 5.9
Connection
Type of connec-
tion
Diagnosis Instance ID
Length
16 DI/DO + DIA
Exclusive owner
Yes
Output: 100
2 byte
Input: 108
8 byte
16 DI/DO + DIA
Input
No
Output: 193
0 byte
Input: 108
8 byte
Generic 16 DI + DIA
Listen only
Yes
Output: 192
0 byte
Input: 104
6 byte
Table 5.10
Connection
Type of connec-
tion
Diagnosis Instance ID
Length
16 DI/DO + DIA + DCU Exclusive owner
Yes
Output: 100
20 byte
Input: 101
25 byte
16 DI/DO + DCU
Exclusive owner
No
Output: 100
20 byte
Input: 102
21 byte
16 DI/DO + DIA + DCU Input only
Yes
Output: 193
0 byte
Input: 101
25 byte
16 DI/DO + DCU
Input only
No
Output: 193
0 byte
Input: 102
21 byte
Table 5.11
Connection
Type of connec-
tion
Diagnosis Instance ID
Length
8 DI/DO + DIA + DCU
Exclusive owner
Yes
Output: 103
19 byte
Input: 104
24 byte
8 DI/DO + DCU
Exclusive owner
No
Output: 103
19 byte
Input: 105
20 byte
Connection
Type of connec-
tion
Diagnosis Instance ID
Length