ICE1-*-G60L-V1D, ICE1-*-G60L-C1-V1D
Commissioning for PROFINET
2
0
1
9
-1
0
55
•
Digital-Out Restart Mode
(supported with 16DIO modules)
Automatic restart after short circuit of digital output or reset of channel diagnosis when
resetting the digital output.
Fail-Safe Configuration
These parameters are provided by module types with digital outputs. When configuring the
modules, you can define the status of the outputs after an interruption or loss of communica-
tion.
The following options are available:
1.
Set Low
- Deactivate the output channel (digital value = 0)
2.
Set High
- Activate the output channel (digital value = 1)
3.
Hold Last
- Hold the last output state (digital value matches last state)
The "Surveillance Timeout" parameter
This parameter is supplied by modules types that produce digital outputs.
The firmware of these modules enables you to set a delay time before the monitoring of the out-
put currents starts, i.e., a surveillance timeout. You can set this for each individual output chan-
nel.
The delay time starts after the status of the output channel changes, i.e., when the channel is
activated (after a rising edge) or deactivated (after a falling edge). After this time has elapsed,
the monitoring of the output begins and the diagnosis begins reporting error states.
The surveillance timeout can be set between 0 ms and 255 ms. The default value is 80 ms.
When the output channel is in a static state, i.e., when the channel is permanently switched on
or off, the value is 100 ms.
IO Mapping Configuration (Only for 16DIO Modules)
Using IO mapping configuration, it is possible to alter the data structure of I/O data. By default,
each I/O channel is represented in order in the process data. Existing PLC programs may use a
different channel assignment
Using these parameters, all I/O channels can therefore be freely assigned to a bit in the I/O
data. It is important to note that double assignments are not possible. If incorrect parameteriza-
tion of the IO mapping is detected when transferring the configuration, the module reports an
error.
Prioritized Start-Up/Fast Start-Up (FSU)
The modules with Fast Start-Up (FSU) support optimized system power-up. This ensures a
quick restart after a power supply is restored after an interruption.
1.
Select "Device View" (1) and the desired module (in this example, slot 1 for a 16DIO module
with 8DI/8DO profile).
2.
Then, in the "General" tab, select the "Advanced Options" area (2).
3.
Click on the "Prioritized Start-Up" option (3) to enable prioritized startup.