Thus, the bit assignment of the data generally follows the following logic:
The values refer to the following:
bus
Number
0 = No connection to fieldbus
1 = Connected to fieldbus
failsafe
Number
0 = Outputs in normal mode
1 = Outputs in failsafe mode
inputs
Number[2]
Byte 0 = Actual status of input port X1
–
X4 (channel A/B)
Byte 1 = Actual status of input port X5
–
X8 (channel A/B)
outputs
Number[2]
Byte 0 = Actual status of output port X1
–
X4 (channel A/B)
Byte 1 = Actual status of output port X5
–
X8 (channel A/B)
consuming
Number[2]
Byte 0 = Data from PLC at port X1
–
X4 (channel A/B)
Byte 1 = Data from PLC at port X5
–
X8 (channel A/B)
producing
Number[2]
Byte 0 = Data sent to PLC at port X1
–
X4 (channel A/B)
Byte 1 = Data sent to PLC at port X5
–
X8 (channel A/B)
diag
Number[4]
Contains module diagnostic data
Byte 0:
•
Bit 0 = Power supply error in the system/sensor (U
s
)
•
Bit 1 = Power supply error in the actuator (U
L
)
•
Bit 2 = Sensor overload
•
Bit 3 = Actuator overload
•
Bit 6 = Force mode active
•
Bit 7 = Internal module error (Invalid IO data)
Byte 1 = Sensor overload at port X1 ... X8
Byte 2 = Actuator overload at port X1 ... X4 (channel A, B)
Byte 3 = Actuator overload at port X5 ... X8 (channel A, B)
dcu
Object
Only available for DCU modules
dcu/state
Number
Current state of the DCU:
•
0 = Locked
•
1 = No program
•
2 = Disabled
•
3 = Stop
•
4 = Run
•
5 = Error
dcu/auto-
start
Number
0 = Local autostart disabled
1 = Local autostart enabled
dcu/public
Number [32] Contains the values of the DCU public variables (_P0
–
_P31)
dcu/con-
suming_bits
Number [2]
DCU 16-bit exchange data set by PLC
dcu/produc-
ing_bit
Number [2]
DCU 16-bit exchange data set by a DCU program
dcu/con-
suming_ints
Number [8]
DCU 16-byte data exchange words set by PLC
dcu/produc-
ing_ints
Number [8]
DCU 16-byte data exchange words set by a DCU program
Table 8.1
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Byte 0
X4-B
X4-A
X3-B
X3-A
X2-B
X2-A
X1-B
X1-A
Byte 1
X8-B
X8-A
X7-B
X7-A
X6-B
X6-A
X5-B
X5-A
Table 8.2
Name
Data Type
Description