8.9 MANUAL EMErGENCy - < EMErGENCy > MENU
Following.is.a.description.of.the.procedure.for.managing.emergencies.manually.by.an.authorised.operator.
8.9.1 General information
The. manual. emergency. mode. can. be. accessed. at. any. time.. It. has. priority. over. any. pre-recorded. messages. being. broadcast. at. the. time.
activated.by.an.external.peripheral.unit.connected.to.a.“Control.Input”.and.over.any.emergency.units.able.to.cover.the.six.output.zones.of.the.
unit.concerned..During.a.Manual.Emergency.(once.access.has.occurred),.the.display.will.show.the.operating.status.of.the.system.as.follows:
8.9.2 recommended procedure for managing emergencies manually
Thanks.to.its.double-channel.operation,.the.PA8506-V.system.enables.structured.management.of.the.alarm.messages,.of.silencing.of.the.
messages.and.of.selection.of.the.zones,.as.illustrated.in.detail.below..Following.is.a.list.of.activities.enabling.a.Manual.Emergency.to.be.
handled.rapidly.
Action required
How to proceed
result
Access.the.system
Press.the.
Emergency
.key.twice
The.zones.will.all.be.selected...
The.
Emergency
key.will.light.up.
Carry.out.an.overall.alarm.reset.
Press.the.RESET.key
The.alarms.will.be.reset,.all.the.zones.will.continue.to.
be.selected..The.alarm.LED.will.extinguish.
Reset.the.
beep
,.if.any,.
for.the.current.failure
Press.the.ESC.key
The.signalling.tone.of.the.monitoring.loudspeaker.will.
be.silenced.
1)
.
Access the Manual Emergency
Send.the.message.to.all.zones.
Press.ALERT.or.EVAC.or.use.the.
Emergency.Microphone
The.message.is.played.out.to.all.the.zones..
The.alarm.LED.will.light.up.
2)
.
despatch of alarm to all zones
Select.the.zones
Press.the.numerical.keys.
to.select.the.zones.
The.selected.zone.will.display.a.flashing.label..
Send.the.message
Press.ALERT.or.EVAC.or..
use.the.
Emergency
.Microphone
The.message.will.be.played.out.to.all.the.zones.
selected..The.alarm.LED.lights.up.
3) Send the alarm to one zone or group of zones
or
•.
Zone status bar:
-.
Empty label
:.no.message.being.broadcast.to.this.zone.
-.
EVAC
:.EVACUATION.message.being.broadcast.to.this.zone.
-.
ALErT
:.ALERT:.ALERT.message.being.broadcast.to.this.zone.
-.
MIC
:.life.announcement.being.broadcast.to.this.zone.with.the.hand-held.
microphone.
-.
dIS
:.zone.disabled.for.alarms,.cannot.be.selected.(see.point.8.6.4).
-.
FAIL
:.zone.with.the.speaker.line.in.a.failed.condition,.shown.even.if.the.type.of.failure.does.not.prejudice.the.output.signal.being.broadcast,.
or.operating.on.a.single.channel.due.to.failure.of.the.amplifier.so.that.the.envisaged.signal.cannot.be.broadcast.to.that.zone..For.details.see.
points.9.2.and.9.3.
•.
Led ALArM
:.
LED.illuminated.to.indicate.that.the.VOICE.ALARM.condition.is.active.when.a.live.announcement.or.the.current.pre-recorded.message.are.being.
broadcast.to.at.least.one.zone.even.if,.in.a.12-zone.system,.the.zone.is.covered.by.the.other.PA8506-V.unit.connected.via.the.REMOTE.LINK.
•.
Labels associated with zones Z1-Z6
:
-.
Zones with white background
:.zone.non.selected..The.current.message,.
if.any,.has.been.activated.automatically.
-.
Zones with black background
:. zone. with. current. message. activated.
manually.
-.
Flashing zones
:.zone.selected,.ready.for.a.message.to.be.sent.
manually.or.to.be.Reset.(see.Note..1).
•.
Title bar
:
-.
EMErGENCy
:.access.achieved.for.a.manual.emergency.
-.
EMErGENCy UNIT #
:.on-going.manual.emergency.activated.by.an.emergency.unit,.with.the.relevant.address,.connected.to.the.EMERGENCY.
UNIT.socket.
-.
rEMOTE UNIT #
:.on-going.manual.emergency.activated.by.an.emergency.unit,.with.the.relevant.address,.connected.to.the.remote.PA8506-V.