8.5.1.6 POWEr SUPPLy FAULTS
Power supply and display memory diagnostics
From.the.FAULTS.panel.(point.8.5.1),.press.numerical.key.4.to.access.the.
panel.for.viewing.the.diagnostics.of.the.primary.and.secondary.power.supplies.
and.of.the.memory.for.managing.the.display.
The.diagnostic.state.of.each.item.monitored.is.reported,.as.shown.in.the.
following.table.
Press.ESC.to.return.to.the.FAULTS.panel.
Label
Part being diagnosed
display
Cause
Action required
All
All
OK
No.failures
-
N.T.
NOT.TEST..Diagnostics.
disabled.during.configuration.
(See.Menu.
set>.
BACKGROUND.TEST)
-
Res.
Failure.cleared.due.to.
previous.failure.signal
Access.the.Report>.FAULTS.panel.from.the.
OPERATOR.menu.and.carry.out.a.MANUAL.
RESET.of.the.FAILURE.signal.
Main.P.S.
Primary.power.supply.
230Vac
Fault
Primary.power.supply..
not.detected
Check.the.230.VAC.power.supply,.the.
connecting.cable.and.the.mains.fuse..
If.the.failure.persists,.call.Servicing.
24Vdc.P.S.
Secondary.power.supply.
24Vdc
Secondary.power.supply.
not.detected
Check.the.external.24.VDC.power.supply.
system..If.the.failure.persists,.call.Servicing.
Display
Memory.managing.
the.graphic.display
Memory.checksum.error
Call.Servicing.
Tab..8.5.1.6