13
System Manual | 2014
PA8500-VES | Voice Evacuation System
UK
PA8506-V
|
VES Compact System
•..
PMB106-G and PMB112-G broadcasting microphone stations
By.connecting.one.or.more.remote.paging.units.to.the.PAGING.UNIT.socket,.it.is.possible.to.manage.the.whole.12-zone.system.for.broadcasting.
announcements
Model.
PMB106-G
has.six.zone-selection.keys.that.can.be.assigned.only.to.the.six.output.zones.of.the.“local”.PA8506-V.unit.to.which.the.station.
is.connected..The.PTT.key.(which.may.be.programmable).functions.in.the.GLOBAL.mode.and.is.assigned.to.selecting.all.12.zones;.model.
PMB112-G
.functions.in.the.GLOBAL.mode.and.has.12.zone-selection.keys.that.can.access.all.12.zones.of.the.system.
The.zone-selection.keys.and.their.LEDs.are.assigned.to.the.output.zones.of.the.system.with.reference.to.the.PA8506-V.unit.connecting.them.
to.the.microphone.station:
-. The.first.zone-selection.group,.numbered.from.1.to.6,.is.assigned.to.the.output.zones.of.the.“local”.PA8506-V.unit.to.which.the.station.is.
connected.
-. The.second.zone-selection.group,.numbered.from.7.to.12,.is.assigned.to.the.output.zones.of.the.“remote”.PA8506-V.unit,.connected.to.the.
“local”.PA8506-V.unit.via.the.REMOTE.LINK.
The.zone-selection.keys.can.also.be.programmed.to.activate.a.group.of.several.output.zones.(see.the.User.Manual.of.the.station),.in.which.
case.the.LEDs.corresponding.to.the.actual.zones.activated.will.light.up.both.at.the.time.of.selection.and.at.the.time.of.the.announcement..The.
figure.shows.how.the.zone-selection.keypads.are.used.
The.signalling.LEDs.of.the.zone-selection.keypad.are.assigned.to.the.output.zones.of.the.system.with.reference.to.the.PA8506-V.unit.connecting.
them.to.the.microphone.station:
-. The.first.group.of.LEDs.of.the.zone-selection.keys.numbered.from.1.to.6,.is.assigned.to.the.output.zones.of.the.“local”.PA8506-V.to.which.
the.station.is.connected.
-. The.second.group.of.LEDs.of.the.selection.keys.numbered.from.7.to.12.is.assigned.to.the.output.zones.of.the.“remote”.PA8506-V.unit,.
connected.to.the.“local”.PA8506-V.unit.via.the.REMOTE.LINK.
The.zone.selection.keys.can.also.be.programmed.to.activate.a.group.of.several.output.zones.(see.point.8.6.4.1.)..In.this.case:
-. When.a.zone.is.selected,.the.green.LED.corresponding.to.the.chosen.key.will.flash.to.indicate.that.the.selection.has.been.made.
-.When.the.output.signal.is.activated,.the.LEDs.corresponding.to.the.actual.zones.activated.will.light.up.on.the.basis.of.the.current.status..