8.6.4
EMErGENCy UNIT CONFIG
Configuring an emergency unit
Panel.for.displaying.and.changing.the.operating.parameters.of.an.emergency.unit...
•.
Adjusting the sensitivity of the microphone
. -. Press.key.
1
.-
Mic attenuation
.and.hold.it.down.
. -. Use.the.+/-.knob.to.set.the.required.level.of.attenuation.within.a.range.from.1.
(maximum.sensitivity).to.30.(minimum.sensitivity).
N.B.:.Once.the.parameter.has.been.set,.it.is.operational.both.in.the.Emergency.
mode.and.in.the.Broadcasting.mode.
•.
Setting the output volume
:
. -. Press.key.
2
.-.
Output level
and.hold.it.down.
. -. Use.the.
+/-
.knob.to.set.the.required.volume.level.within.a.range.from.
–6
.(minimum.output.level).to.
+21
.(maximum.output.level).
N.B.:. The. parameter. set. is. operational. only. in. the. Emergency. mode.. To. set. the. volume. for. the. Broadcasting. mode,. see. under. “AUDIO.
SETTING>.
•.
diagnostic settings:
. -. Press.key.
3
.–.
Test
.cyclically.
. . >..OFF:.diagnostics.disabled
. . >..ON:.diagnostics.enabled
N.B.:.The.addresses.of.the.stations.for.which.diagnostics.have.been.disabled.remain.in.any.case.in.the.configuration.of.the.acquired.system.
•.
Setting the 6-zone or 12-zone operating mode:
In.a.12-zone.system.with.two.PA8506-V.units.connected.to.one.another,.it.is.possible.to.configure.these.stations.for.operation.limited.to.the.6.
zones.covered.by.the.unit.in.question.or.extended.to.all.12.zones.within.the.system.as.a.whole..
-. Press.key
4
.–.
Mode
.cyclically.
. >.GLOBAL:.When.a.microphone.station.is.in.the.Global.mode,.it.can.be.used.to.make.selective.announcements.or.general.announcements.in.
all.12.zones.of.the.system..Access.is.governed.by.the.priority.settings.of.all.the.“Global”.or.“Local”.stations.connected.to.the.two.
PA8506-V.units.
. >.LOCAL:. When.a.microphone.station.is.in.the.Local.mode,.it.can.be.used.to.make.selective.announcements.or.general.announcements.
only.to.the.zones.covered.by.the.local.PA8506-V.unit.to.which.it.is.connected..This.mode.enables.another.“Local”.microphone.
station.connected.to.the.other.PA8506-V.unit.to.make.announcements.to.the.six.zones.it.covers.at.the.same.time..Access.is.
governed.by.the.priority.settings.of.all.the.stations.connected.to.the.PA8506-V.unit.with.which.they.are.associated.and.to.those.of.
the.other.PA8506-V.unit.that.are.set.in.the.“Global”.mode...
N.B.:.To.manage.the.system.correctly,.it.is.suggested.that.priority.levels.set.for.the.“Global”.microphone.bases.should.be.higher.than.those.set.for.the.
“Local”.microphone.bases..In.any.case,.the.PA8506-V.unit.with.its.own.hand-held.emergency.microphone.connected.to.the.front.panel.is.configured.for.
LOCAL.operation.and.with.the.highest.level.of.priority,.higher.than.any.remote.station.of.the.PMB132.range.
•.
Setting the level of the 20 kHz test tone:
This.control.adjusts.the.level.of.the.20.kHz.test.tone.generated.by.the.microphone.
station. so. as. to. offset. any. losses. of. the. signal. in. the. event. of. long-distance.
connections.
-. Press.key.6..The.line.“20.kHz.level”.will.appear,.followed.by.a.six-bar.vu-meter.
showing.the.value.set.for.the.test.signal..It.is.advisable.to.set.the.level.in.such.a.
way.that.at.least.two.or.three.bars.of.the.vu-meter.are.active.
-. Hold.down.key.6.and.use.the.+/-.knob.to.set.the.required.level,.within.a.range.
from.0.to.200.
N.B..The.change.in.the.level.shown.by.the.vu-meter.will.not.occur.immediately..After.
setting.the.level,.wait.for.about.30.seconds.before.reading.it.again.
•.
Priority
The.priority.level.set.for.the.microphone.station.is.shown.on.the.bottom.line.to.the.left..The.values.can.vary.between.8.(lowest.priority).and.14.
(maximum.priority)..The.parameter.is.displayed.only..To.change.its.value,.consult.the.manual.of.the.PMB132-V.and.PMB132/12-V.stations.(code.
no..11/716,.point.4.2).
•.
Low Cut Filter
The.setting.of.the.LOW.CUT.filter.is.shown.on.the.bottom.line.at.the.centre.
>.LCON:.filter.active
>.LCOFF:.filter.not.active
This.parameter.is.only.displayed..To.change.its.value,.consult.the.manual.of.the.PMB132-V.and.PMB132/12-V.stations.(code.no..11/716,.point.
4.6).
•.
P.T.T. Toggle
The.toggle.mode.of.the.PTT.key.is.shown.on.the.bottom.line.on.the.right-hand.side.
PTT:.Toggle.OFF.
LOCK:.Toggle.ON
Note:
.The.setting.of.this.parameter.is.operational.only.in.the.Broadcasting.mode..In.Emergency.conditions.the.Toggle.mode.is.always.OFF..This.parameter.
is.only.displayed..To.change.its.value,.consult.the.manual.of.the.PMB132-V.and.PMB132/12-V.stations.(code.no..11/716,.point.4.3).