54
PA8506-V
|
VES Compact System
PA8500-VES | Voice Evacuation System
System Manual | 2014
UK
8.7.4
ALArM LEVEL
Adjustment of the volume of VES sources
Panel.for.adjusting.the.output.volume.of.VES.sources.for.the.purpose.of.calibrating.
the.system..
To.adjust.the.volume.of.the.required.source:.
•.hold.the.corresponding.numbered.key.(1.-.5).down.
..
and
•.use.the.+/-.knob.to.adjust.the.volume.
Note:.The.volume.set.will.be.the.same.for.all.the.output.zones.
Upon.completion,.press.ESC.to.return.to.the.CONFIGURATION.menu.
1-Output volume of the pre-recorded ALErT message:
.the.range.within.which.the.ALERT.MESSAGE.can.be.set.is.comprised.between.
-20.dB.to.0.dB.
2-Output volume of the pre-recorded EVACUATION message:
.the.range.within.which.the.EVAC.MESSAGE.can.be.set.is.comprised.between.
-20.dB.to.0.dB.
3-Output volume of the Hand-held Emergency Microphone:
.the.range.within.which.the.FIRE.MICROPHONE.can.be.set.is.comprised.between.
0.dB.and.+20.dB.(in.most.cases.it.is.suggested.that.a.level.of.+16.dB.should.not.be.exceeded).
4-Output volume from the Emergency Units connected to the Local PA8506-V unit:
the.setting.range.for.the.EMERGENCY.UNITS.is.between.
-20.dB.and.+10.dB.
5-Output volume from the Emergency units connected to the remote PA8506-V unit:
the.setting.range.for.REMOTE.LINKS.is.between.-20.dB.
and.+10.dB.
8.7.5
AMPLIFIEr MOdE
Amplification system operating modes
Panel.for.setting.the.operating.mode.of.the.system.in.relation.to.its.configuration.
with.a.possible.external.amplifier.for.increasing.its.power..To.configure.the.system,.
refer.to.the.contents.of.points.5.1.1.and.5.1.2.
•.Use.the.+/-..knob.directly.to.choose.between.the.following:
>.
NO EXT. AMPLIFIEr
for.a.PA8506-V.with.no.external.amplifier
>.
WITH EXT. AMPLFIEr
.for.a.PA8506-V.with.an.external.amplifier
•.press.OK.to.confirm.the.setting.
Upon.completion,.press.ESC.to.return.to.the.CONFIGURATION.menu.
8.7.6
IP AddrESS
Setting the networking parameters
Panel.for.setting.the.networking.parameters.for.accessing.the.system.functions.via.
Web.Server..The.MAC.code.includes.the.physical.address.of.the.networking.card..
It.is.possible.to.change.the.IP.address.to.adapt.it.to.the.local.network.to.which.the.
system.is.connected.and.the.MASK.address.for.any.sub-networks.
•. Use.numerical.keys.5.or.6.to.select.the.code.to.be.altered,.
IP
.or.
MASK
.
•. Hold.down.the.keys.from.1.to.4.one.at.a.time.and.use.the.+/-..knob.to.change.the.
four.fields.of.the.address.code.
•. Upon. completion,. press. OK. to. confirm. the. setting. and. return. to. the.
CONFIGURATION.menu.
8.7.7
PASSWOrd
Setting the password
Panel. for. enabling,. disabling. and. customising. the. password. for. accessing. the.
system.service.levels.
•.. Use.the.+/-..knob.to.position.the.cursor.on.each.digit.of.the.password.to.be.
changed
•. Use.the.numerical.keys.(1-6).to.enter.the.new.password
•. Press.OK.to.enable.or.disable.the.password.as.set.
Note:
The display will show the new password programming that has been set.
In.order.to.recover.the.password,.e.g..if.it.has.been.forgotten,.it.will.be.necessary.to.
access.the.system.via.the.web.server.in.the.Service.mode,.requesting.assistance.
Upon. completion. of. the. activity,. press. ESC. to. return. to. the. CONFIGURATION.
menu.
Summary of Contents for PA8506-V
Page 2: ......
Page 4: ... PA8506 V VES Compact System PA8500 VES Voice Evacuation System System Manual 2014 UK ...
Page 66: ......
Page 67: ......