19
System Manual | 2014
PA8500-VES | Voice Evacuation System
UK
PA8506-V
|
VES Compact System
C1.
.
Monitoring/beep loudspeaker
.
Built-in.loudspeaker.that,.in.quiescent.conditions,.can.be.used.as.a.preliminary.monitoring.loudspeaker,.since.it.can.select.the.sources.
reaching.the.routing.section.or.the.voice.and.music.channels.sent.to.the.amplifiers..The.volume.can.be.adjusted.within.a.range.from.-10db.
to.+10dB.in.respect.of.the.volume.set.for.the.selected.input..Regardless.of.the.manual.setting.of.the.monitor,.the.PA8506-V.system.will.
use.the.loudspeaker,.with.top.priority,.for.acoustic.signalling.(beep).of.any.failures.detected..It.will.be.muted.when.the.failure.conditions.
cease.to.exist...In.addition,.in.order.to.avoid.the.Larsen.effect,.it.will.be.muted.by.the.system.during.use.of.the.Emergency.Microphone..
The.output.volume.of.the.signalling.tone.will.be.at.its.highest.level.for.failures.detected.while.the.system.is.operating,.while.it.will.be.at.
the.level.set.previously.for.the.monitor.in.the.event.of.a.System.Fault.(CPU.Fault).
C2.
.
rESET button
.
Key.for.resetting.the.pre-recorded.emergency.messages.manually,.operational.during.Manual.Emergencies..Key.for.resetting.the.buzzer.
and.for.cancelling.signalling.of.the.failure,.operational.when.there.is.a.failure.present.or.after.a.failure.has.been.cleared..In.the.idle.condition,.
this.key.is.not.operational.
C3.
.
ALErT button
.
Key.for.sending.pre-recorded.Alert.messages.manually,.operation.during.Manual.Emergencies..In.the.idle.condition.this.key.is.not.
operational.
C4.
.
EVAC button
.
Key.for.sending.pre-recorded.Evacuation.messages.manually,.operational.during.Manual.Emergencies..In.the.idle.condition.this.key.is.
not.operational.
C5.
.
MENU key
.
Multi-purpose.key.for.accessing.the.Main.Page,.for.navigating.among.the.menus.and.for.specific.functions.of.the.submenus.indicated.on.
the.displays.
C6.
.
OK key
.
Multi-purpose.key.for.confirming.selections,.for.navigating.among.the.menus.and.for.specific.functions.of.the.submenus.indicated.on.the.
displays.
C7.
.
ESC key
.
Multi-purpose.key.for.returning.to.the.Music.menu,.for.navigating.among.the.menus.and.for.specific.functions.of.the.submenus.indicated.
on.the.displays.
C8.
.
Numerical keys from 1 to 6
.
Multipurpose.keys,.operational.throughout.the.system..These.keys.are.used.to.select.the.zones,.from.1.to.6..For.the.PA8506-V.unit.being.
used..They.enable.the.access.password.to.be.entered.or.the.specific.functions.indicated.on.the.status.bar.on.the.display.to.be.applied.
C9. Status signalling
.
•.
ALArM LEd (red)
.
LED.for.signalling.the.existence.of.a.“Voice.Alarm.Condition”..A.VOICE.ALARM.condition.can.be.activated.both.automatically.from.
an.external.peripheral.unit,.and.manually.by.the.operator.of.the.PA8506-V.or.of.an.emergency.microphone.station..When.the.LED.is.
illuminated.steadily,.this.indicates.that.a.pre-recorded.or.live.emergency.message.is.being.broadcast.to.at.least.one.zone.(of.the.whole.
system,.also.when.it.includes.12.zones)..During.the.VOICE.ALARM.condition,.the.standard.functions.for.playing.out.music.and.the.voice.
source.service.are.disabled..In.the.“Quiescent.condition”.the.ALARM.LED.is.extinguished.
.
•..
FAULT LEd (yellow)
.
LED.for.signalling.the.existence.of.a.“Fault.condition”..This.indicates.that.the.diagnostic.system.has.detected.at.least.one.failure.in.the.
PA8506-V.unit.or.in.one.of.the.items.of.equipment.connected.to.it.and.covered.by.the.diagnostic.procedure..When.the.fault.condition.is.
cleared,.the.FAULT.LED.extinguishes.automatically.and.the.wording.“RES”.is.shown.on.the.FAULTS.display,.to.show.that.a.failure.has.
been.detected.and.subsequently.remedied.(RESOLVED)..The.LED.signalling.that.the.fault.has.been.cleared.will.extinguish.once.the.
MANUAL.FAULT.RESET.procedure.has.been.completed..In.a.12-zone.system.with.two.PA8506-V.units.connected.to.one.another,.if.the.
LED.flashes,.this.indicates.the.presence.of.at.least.one.current.failure.referred.to.the.other.remote.PA8506-V.or.to.an.item.of.equipment.
connected.to.it.and.covered.by.the.diagnostic.procedure.
6.2.3 Control panel
Summary of Contents for PA8506-V
Page 2: ......
Page 4: ... PA8506 V VES Compact System PA8500 VES Voice Evacuation System System Manual 2014 UK ...
Page 66: ......
Page 67: ......