18
PA8506-V
|
VES Compact System
PA8500-VES | Voice Evacuation System
System Manual | 2014
UK
r11.
.
IN. 1 – MIC 1
.
INPUT.1.input.for.an.external.microphone,.programmable.as.a.Music.or.Voice.source..It.is.possible.to.connect.dynamic.or.electret.
microphones.to.this.input,.enabling.the.phantom.power.supply..This.input.can.be.set.in.many.different.ways.based.on.how.the.operating.
mode.is.programmed:..
.
-. enabled.directly.as.a.Music.or.Voice.source,.
.
-. mixed.with.input.2.(IN..2)..
.
-. as.a.Voice.source.enabled.by.the.precedence.contact.(PREC.),.with.a.CHIME.that.can.be.activated/de-activated...
.
When.it.is.used.as.a.Voice.source,.it.is.possible.to.set.priority,.to.7.different.levels,.and.the.group.of.paging.zones..The.XLR.-F.socket.
enables.a.balanced.signal.of.up.to.100.mV.to.be.connected,.by.means.of.shielded.balanced.microphone.cable..For.details.concerning.
the.settings.of.the.IN..1.input,.refer.to.the.indications.contained.in.the.INPUT.1.and.CHIME.of.the.AUDIO.SETTING.menu.and.in.the.
MUSIC.menu.
r12.
.
AUX IN
.
Input.for.connecting.an.external.source.of.music..It.has.one.pair.of.RCA.sockets,.with.conversion.to.mono,.for.sources.with.unbalanced.
outputs.at.line.level..For.the.audio.settings.of.the.AUX.input,.refer.to.the.information.contained.in.the.MUSIC.menu.
r13.
.
Plug for 230 VAC mains power with built-in fuse
.
Plug.for.connecting.the.equipment.to.the.230.VAC/50-60Hz.mains.power.using.the.power.cable.supplied.with.it..If.it.is.necessary.to.
replace.the.mains.fuse,.this.must.be.done.with.one.of.the.same.type,.i.e..6.3.A.fuse,.of.the.miniature.20.mm.cylindrical.type..(Consult.
the.“Power.supply.and.earthing”.and.“Safety.Notes”.sections.for.details.about.safety).
r14.
.
Frame connection
.
The.frame.connection.may.be.used.to.connect.other.equipment.only.for.the.purpose.of.shielding.the.low.signals..This.terminal.may.not.
be.used.to.connect.the.frame.to.earth.for.safety.purposes..(Consult.the.“Power.supply.and.earthing”.and.“Safety.Notes”.sections.for.
details.about.safety).
r15.
.
Fuse for external 24 VdC power supply
.
32.A.fuse,.cylindrical.type,.10x38.mm,.and.fuse-holder.with.bayonet.coupling..This.fuse.must.be.replaced.solely.with.another.identical.
one.(Consult.the.“Power.supply.and.earthing”.and.“Safety.Notes”.sections.for.details.about.safety).
r16.
.
rELAy 1 – rELAy 2
.
2.relay.outputs.for.signalling.to.external.peripheral.units..The.PA8506-V.system.enables.the.logical.outputs.to.be.programmed.to.link.
activation.of.the.output.with.system.status.events.or.for.override.functions.in.connection.with.emergency.conditions,.or.for.signalling.
failures,.emergencies.and.disabling..By.default,.the.RELAY.2.output.is.programmed.to.signal.CPU.failures.(SYS.Fault).in.the.normally.
de-activated.condition..All.the.outputs.can.be.programmed.as.Normally.Active.or.Normally.De-activated...The.connection.provides.3.
screw-down.terminals.for.stripped.wires.for.each.relay,.referred.to.the.N.O.,..N.C..and.exchange.contacts.
r17.
.
EXT. AMP. IN
.
.
Input.socket.for.connection.of.the.optional.external.amplifier.PASO.ref..AW5624..This.enables.the.system.to.be.expanded,.increasing.
the.available.power.up.to.a.total.of.490W..Connect.the.constant-voltage.power.output.of.the.amplifier.to.the.terminals.provided.for.the.
0V-70V.and.100V.signals.of.a.PA8506-V.unit..In.a.12-zone.system.with.two.PA8506-V.units.connected.to.one.another,.do.not.use.a.
single.expansion.amplifier.for.both.PA8506-V.units..Rather,.install.two.separate.amplifiers..In.this.case.the.total.output.power.of.the.
system.will.be.980.W.
r18.
.
LOUdSPEAKEr OUTPUTS
.
Power.outputs.for.the.loudspeaker.lines..Use.only.speaker.units.with.constant-voltage.100.V.line-repeating.coils...6.output.zones.are.
available,.each.of.which.is.split.up.into.2.lines,.A.and.B,.for.creating.the.network.of.loudspeakers.with.double.lines.for.redundancy..In.the.
event.of.a.short.circuit.of.one.line,.the.PA8506-V.system.will.de-activate.the.failed.line.and.continue.to.power.the.other.line.of.the.same.
zone,.activating.the.failure.signalling..12.pairs.of.screw-down.terminals.for.cables.with.a.cross-section.of.up.to.2.5.mm
2
.are.available.for.
connecting.the.0.V.to.100.V.lines.
r19.
.
CONTrOL INPUTS
.
8.digital.inputs.for.monitoring.via.external.peripheral.units..They.enable.programmed.events.to.be.activated,.including.switching.of.the.
PA8506-V.system.to.a.Voice.Emergency.condition,.requiring.automatic.sending.of.pre-recorded.emergency.messages..Activation.is.
possible.by.means.of.Normally.Open.or.Normally.Closed.contacts,.relaying.the.+24.VDC.voltage.supplied.from.the.service.sockets..It.
is.possible.to.enable.diagnostics.of.the.connecting.stretch,.arranging.to.install.two.10-kOhm.balancing.resistors.in.the.proximity.of.the.
contact.for.activating.the.remote.peripheral.unit..The.connection.provides.11.screw-down.terminals.for.stripped.wires:.eight.off.control.
inputs.and.three.off..+24.VDC.service.sockets.
r20.
.
CONTrOL OUTPUTS
.
6.open-collector.outputs.for. driving.generic.external. or.peripheral.relays.. The.PA8506-V. system. enables. the.logical.outputs.to.be.
programmed.to.link.activation.of.the.output.with.system.status.events.or.for.override.functions.in.emergency.conditions.or.for.signalling.
failures.relating.to.the.current.emergency.and.to.the.disablement..These.outputs.can.be.programmed.as.Normally.Open.or.Normally.
Closed.and.they.have.internal.24.VDC.voltage.with.automatically.resetting.protection.devices..The.connection.provides.eight.screw-
down.terminals.for.stripped.wires:.six.off.max..200.mA.open-collector.outputs.and.two.off.+24.VDC.service.sockets.