8.6.2
CONTrOL OUTPUT
.
Local output contacts
Panel.for.programming.the.six.local.output.contacts.(CONTROL.OUTPUTS).
and.the.two.service.relays,.RELAY.1.and.RELAY.2.
For.each.output.it.is.possible.to.choose.the.idle.status.and.to.associate.the.
system.status.event.leading.to.its.activation.
On.completing.the.programming,.press.ESC.to.return.to.the.OPERATOR.
menu.
8.6.2.1
.
Programming the output contacts
Note:.The.display.will.show.the.programming.that.has.been.set.
Choosing the output to be programmed:
Hold.the.OUT.key.(
1
).down.and.turn.the.
+/-
.knob.to.select.the.number.of.the.output.from.among.the.following:
.
>.
OPEN COL. outputs from 1 to 6:
.open-collector.CONTROL.OUTPUTS.
.
>.
rELAy AUX outputs from 1 to 2:
.RELAY.1.and.RELAY.2.OUTPUTS.
Programming an output to associate it with a system event:
Hold.the.MODE.key.(
2
).down.and.turn.the.
+/-
.knob.to.select.one.of.the.following.options:.
.
.
.
>.
USEr MOdE:
unprogrammed.output.
.
>.
Override Z1 - Z6:
.seizing.of.the.zone.indicated.by.a.PA.Source.or.a.VES.source.
.
>.
Voice Alarm State:
system.currently.in.a.generic.“Voice.Alarm.Condition”.
.
>
Manual Voice Alarm:
.system.currently.in.a.“Voice.Alarm.Condition”.activated.by.a.Manual.Emergency.(Operator).procedure.
.
>.
Automatic Voice Alarm:
.system.currently.in.a.“Voice.Alarm.Condition”.activated.by.an.Automatic.Emergency.(Control.Input).procedure..
>.
Z1- Z6
.
Voice Alarm:
.system.currently.in.a.“Voice.Alarm.Condition”.affecting.the.output.zone.indicated.
.
>.
Evac Message Playing:
.system.currently.in.a.“Voice.Alarm.Condition”.with.the.pre-recorded.Evac.message.being.played.out.
.
>.
Alert Message Playing:
.system.currently.in.a.“Voice.Alarm.Condition”.with.the.pre-recorded.Alert.message.being.played.out.
.
>.
disablement Condition:
currently.in.a.“Disablement.Condition”.
.
>.
General Fault:
.currently.in.a.generic.“Fault.Warning.Condition”.
.
>.
Fault - Loudspk. Line:
at.least.one.speaker.line.currently.in.a.“Fault.Warning.Condition”.
.
>
Fault - Voice Alarm:
at.least.one.VES.source.currently.in.a.“Fault.Warning.Condition”.
.
>.
Fault - Amplifier:
.at.least.one.amplifier.currently.in.a.“Fault.Warning.Condition”.
.
>.
Fault - Main Powerr:
.main.230.VAC.power.supply.currently.in.a.“Fault.Warning.Condition”.
.
>.
Fault - 24 VdC:
.secondary.24.VDC.currently.in.a.“Fault.Warning.Condition”.
.
>.
Fault - Control Input:
.at.least.one.local.input.contact.currently.in.a.“Fault.Warning.Condition”.
.
>.
Fault - Emerg. Unit:
.at.least.one.emergency.microphone.station.currently.in.a.“Fault.Warning.Condition”.
.
>.
Fault Line Z1 - Z6:
.one.of.the.speaker.lines.pertaining.to.the.zone.indicated.currently.in.a.“Fault.Warning.Condition”.
.
>.
reply Input 1-8:
.the.input.contact.indicated.is.in.an.active.condition...
.
.
......This.also.applies.to.inputs.that.are.not.programmed.or.that.are.inhibited.by.a.higher.priority.
.
>
reply any Input:
.any.input.contact.is.in.an.active.condition...
.
.
.......This.also.applies.to.inputs.that.are.not.operational.or.that.are.inhibited.by.a.higher.priority.
Choice of the idle condition of an output with regard to the activating event (excluding the USEr MOdE):
Press.the.STATE.key.(6).to.select:
.
>.
Normal State OFF:
.output.de-activated.if.the.event.is.not.active.
.
>.
Normal State ON:
.output.active.if.the.event.is.not.active.
•..
Programming of the output contact to signal a System fault (System CPU Fault):
The.RELAY.2.output.can.also.be.programmed.to.signal.a.“System.fault”.detected.by.the.watchdog.system...
After.selecting.the.RELAY.2.output:2:
•.Press.W-D.key.(5).to.select:
>
watch dog OFF
for.an.output.not.programmed.to.signal.System.faults,
or
>.
watch dog ON
for.an.output.programmed.to.signal.System.faults.
Note:
.If.the.output.is.programmed.as.“watchdog.ON”,.the.idle.condition.of.the.output.can.only.be.“Normal.State.OFF”.