39
System Manual | 2014
PA8500-VES | Voice Evacuation System
UK
PA8506-V
|
VES Compact System
8.5.1.7 CONTrOL INPUT FAULT
diagnostics of the local control inputs
From.the.FAULTS.panel.(point.8.5.1),.press.numerical.key.5.to.access.the.
panel. for. viewing. the. diagnostics. of. the. local. control. inputs. (CONTROL.
INPUTS).
The.diagnostic.state.of.each.item.monitored.is.reported,.as.shown.in.the.
following.table.
Press.ESC.to.return.to.the.panel.FAULTS.
Tab. 8.5.1.7
Label
Part being diagnosed
display
Cause
Action required
No.input..
fault.found
Input.contacts.
1.to.8
Empty.
list
No.failure,.or.monitoring.not.
enabled.for.any.input.contacts
-
Input.in.fault:
List.
number.of.
inputs
Break.or.short.circuit.in.the.line.
connecting.the.contact.
Check.integrity.of.the.line.connecting.the.
balancing.resistors.and.the.activation.contact..
If.the.problem.persists,.disconnect.the.line.
connecting.the.activation.contact.and.connect.
a.20.k
W
.resistor.between.the.+24V.service.
terminals.and.the.control.input..If.the.problem.
persists,.contact.Servicing.
Inputs.fault.
resumed:
Failure.cleared.due.to.previous.
failure.signal
Access.the.Report>.FAULTS.panel.from.the.
OPERATOR.menu.and.carry.out.a.MANUAL.
RESET.of.the.FAILURE.signal.
General.Input.
Fault:
Empty.
list
Failure.of.the.internal.communi-
cation.between.the.CPU.and.the.
inputs.controlled.stage.
If.the.problem.persists,.contact.Servicing.
General.Fault.
resumed:
Failure.cleared.due.to.previous.
failure.signal
Access.the.Report>.FAULTS.panel.from.the.
OPERATOR.menu.and.carry.out.a.MANUAL.
RESET.of.the.FAILURE.signal.
8.5.1.8 COMMUNICATION FAULT
.
diagnostics of the internal data communication
From.the.FAULTS.panel.(point.8.5.1),.press.numerical.key.6.and.access.the.
panel.for.viewing.the.diagnostics.of.the.internal.data.communication.
The. diagnostic. state. of. each. item. monitored. is. reported. in. the. following.
table.
Press.ESC.to.return.to.the.panel.FAULTS.
Label
data being diagnosed
display
Cause
Action required
I2C.line
Management.data.of.
amplifiers.and.keys.
interface.
All
OK
No.failure.
-
Audio.SPI.line
Management.data.of.
audio.matrix..
N.T.
NO.TEST..Diagnostics.disabled.
during.configuration.(see.
set>.
BACKGROUND.TEST).
-
Relay.SPI.line
Management.data.of.
outputs.switching.section.
Res.
Failure.(Fault.signal).cleared.
Access.the.Report>.FAULTS.panel.from.the.
OPERATOR.menu.and.carry.out.a.MANUAL.
RESET.of.the.FAILURE.signal.
Fault
Current.failure.due.to.
communication.data.error.
Contact.Servicing.
Tab. 8.5.1.8