44
PA8506-V
|
VES Compact System
PA8500-VES | Voice Evacuation System
System Manual | 2014
UK
8.6.3
BACKGrOUNd TEST
.
Setting the background tests
Panel.for.enabling.and.disabling.background.testing.of.the.critical.sources.
affecting.the.ability.of.the.system.to.function.in.emergency.conditions..The.
categories. for. choosing. the. items. subjected. to. diagnostics. are. listed. as.
shown.in.the.figure.opposite.
•.. The.categories.for.choosing.the.items.subjected.to.diagnostics.are.listed.
as.shown.in.the.figure.opposite.
. >.2-Voice.Alarms.
see.point.8.6.3.1
. >.3-Amplifiers.
see.point.8.6.3.2
. >.4-Power.Supply. see.point.8.6.3.3
. >.6-Communication. see.point.8.6.3.4
or
press.ESC.to.return.to.the.OPERATOR.panel.
8.6.3.1 VOICE ALArM TEST
Setting the Test for Emergency Sources
Panel. for. enabling. and. disabling. background. testing. of. the. “Hand-held.
Emergency.Microphone”.and.the.“Manual.Emergency.Access.Key”.
•. Press.the.appropriate.numerical.key.to.enable.or.disable.the.
diagnostic.test:
>.1-Fire.Microphone:.
on
.(test.enabled).-.
off
(test.disabled)
>.2-Evac.Message:.
on
.(test.enabled).-.
off
(test.disabled)
>.3-Alert.Message:.
on
.(test.enabled).-.
off
(test.disabled)
>.5-Emerg..Button:.
on
.(test.enabled).-.
off
(test.disabled)
>.6-Remote.Link:.
on
.(test.enabled).-.
off
(test.disabled)
Note:.The.display.will.show.the.programming.that.has.been.set.
Press.ESC.to.return.to.the.BACKGROUND.TEST.panel.
8.6.3.2 AMPLIFIEr TEST
Setting the tests for the Amplifiers
Panel.for.enabling.and.disabling.background.testing.of.the.internal.“Voice”.and.
“Music”.amplifiers,.of.the.“External”.amplifier.and.of.the.circuit.for.checking.
insulation.of.the.lines.with.regard.to.dispersion.to.earth.(GND.Fault)..
•...Press.the.appropriate.numerical.key.to.enable.or.disable.the.diagnostic.
test:
>.1-Test.voice.amp.:.
on
.(test.enabled).-.
off
(test.disabled)
>.2-Test.music.amp:.
on
.(test.enabled).-.
off
(test.disabled)
>.3-Test.ext..amp:.
on
.(test.enabled).-.
off
(test.disabled)
>.6-Test.gnd.fault:..
on
.(test.enabled).-.
off
(test.disabled)
Note:.The.display.will.show.the.programming.that.has.been.set.
Press.ESC.to.return.to.the.BACKGROUND.TEST.panel.
8.6.3.3 POWEr SUPPLy TEST
Setting the test for the Power Supplies
Panel. for. enabling. and. disabling. background. testing. of. the. primary. 230.
VAC.power.supply,.the.secondary.24.VDC.power.supply.and.the.memory.
for.managing.the.display.
•.. Press.the.appropriate.numerical.key.to.enable.or.disable.the.diagnostic.
test:
.>.1-Main.P.S.:..
on
.(test.enabled).-.
off
(test.disabled)
>.2-24Vdc.P.S.:.
on
.(test.enabled).-.
off
(test.disabled)
>.6-Display:..
on
.(test.enabled).-.
off
(test.disabled)
Note:.The.display.will.show.the.programming.that.has.been.set.
Press.ESC.to.return.to.the.BACKGROUND.TEST.panel.