15
System Manual | 2014
PA8500-VES | Voice Evacuation System
UK
PA8506-V
|
VES Compact System
6.1.2 Glossary
Following.is.a.list.of.definitions.of.terms.used.in.this.manual,.completed.by.indications.of.a.general.nature.
“BGM Source”
:.
One.of.the.following.audio.sources.using.the.“Music”.amplification.channel.(BackGround.Music):
-. Audio.source.connected.to.the.AUX.input.
-. Flash.memory.device.containing.*.mp3.files.plugged.into.to.the.front-panel.USB.EXT.socket.
-. Sorgente.audio.collegata.all’ingresso.IN.1.(Microfonico).con.modalità.impostata.MODE:.IN.OFF.
-. Sorgente.audio.collegata.all’ingresso.IN.2.(Microfonico.oppure.di.Linea).con.modalità.impostata.MODE:.IN.OFF..
-. One.of.the.BGM.sources.mentioned.above.(USB-AUX-IN.1-IN.2).connected.to.and.selected.for.the.remote.PA8506-V.unit,.and.available.on.
the.local.PA8506-V.unit.via.the.REMOTE.LINK.
During.a.“Voice.Alarm.Condition”,.the.BGM.sources.are.not.operational.
“PA Source”
:.
One.of.the.following.audio.sources.using.the.”Voice”.amplification.channel.for.Public.Address.announcements:
-. Source.of.sound.connected.to.the.IN.1.input.(Microphone.input),.set.in.the.ON.or.PRECEDENCE.MODES.
-. Source.of.sound.to.the.IN.2.input.(Microphone.or.Line.input),.set.in.the.ON,.VOX.or.PRECEDENCE.MODES.
-. Source.of.sound.connected.to.the.IN.3.input.(Line),.set.in.the.ON.or.VOX.MODE.
-. EMERGENCY.UNIT.in.the.broadcasting.mode,.PAGING.UNIT.
-. One.of.the.above.PA.sources.(PAGING.UNIT.or.EMERGENCY.UNIT).connected.to.the.remote.PA8506-V.unit.and.active.on.the.local.PA8506-
V.unit.via.the.REMOTE.LINK.
During.a.“Voice.Alarm.Condition”.the.PA.sources.are.not.operational.
“VES Source”
:
One. of. the. following. audio. sources,. using. the. “Voice”. and/or. “Music”. channels. for. emergency. voice. announcements. (Voice. Evacuation.
System):..
-. Pre-recorded.Alert.message.(ALERT).
-. Pre-recorded.Evacuation.message.(EVAC).
-. Emergency.Microphone.(P.T.T.).connected.to.the.front-panel.MICROPHONE.socket.
-. Emergency.microphone.station.connected.to.the.rear-panel.EMERGENCY.UNITS.socket.
-. One.of.the.VES.sources.indicated.above.(ALERT-.EVAC.–.PTT.–.EMERG..UNITS).connected.to.the.remote.PA8506-V.unit.and.active.on.
the.local.PA8506-V.unit.via.the.REMOTE.LINK.
Activation.of.a.“VES.source”.generates.an.operational.“Voice.Alarm.Condition”..
“Voice channel”
:
Amplification.channel.of.the.PA8506-V.system.using.the.internal.Voice.amplifier.and.the.additional.external.amplifier..
-. During.a.“Quiescent.condition”.it.is.used.by.the.“PA.sources”.
-. During.a.“Voice.Alarm.Condition”.it.is.used.by.the.Emergency.Microphone.or.to.play.out.the.pre-recorded.Evacuation.Message.(EVAC).
“Music Channel”
:
Amplification.channel.of.the.PA8506-V.system.that.uses.the.internal.Music.amplifier..
-. During.a.“Quiescent.condition”.it.is.used.by.the.“sources.of.BGM”.
-. During.a.“Voice.Alarm.Condition”.it.is.used.to.play.out.the.pre-recorded.Alert.message.(ALERT).
“Priority”
:
Use.of.the.output.zones.by.an.audio.signal.or.by.a.reset.command.is.governed.in.the.hierarchy.by.the.level.of.priority.assigned.to.each.active.
source..A.current.activation.of.a.zone.can.be.interrupted.only.by.another.with.a.higher.priority.
The PA8506-V system manages priorities as shown in the following tables:
Priority
System
condition
Operating
enviroment
Priority
level
Active
source
For setting see
MENU
high
low
“
Voice alarm
condition
”
Manual.
Emergency
15
PA8506-V.with.emergency.microphone
Fixed.setting
from.8.to.14 Emergency.microphone.stations
See.the.manual.of.the.PMB132-V,.PMB132/12-V
Automatic.
Emergency
7
CONTROL.INPUT.for.RESET.function
Fixed.setting
6
CONTROL.INPUT.for.EVAC.message.
Fixed.setting
5
CONTROL.INPUT.for.ALERT.message.
Fixed.setting
high
low
“
Quiescent
condition
”
PA.
Source
from.8.to.14 Emergency.units.in.broadcast.mode
See.Emergency.units.manual
from.1.to.7
Inputs IN 1 - IN 2 - IN 3 with the PRECEDENCE
or VOX functions
See.AUDIO.SETTING.section
PAGING.UNITS..Microphone.stations
See.the.manual.of.PMB106-G.and.PMB112-G.
BGM.
Source
0
Music.source
Fixed.setting
The active sources in the “Voice Alarm” condition always have priority over those active in “Quiescent” condition, regardless of the priority level set.