5.3 LOCAL OUTPUT CONTACTS
Examples.of.connection.of.the.control.outputs.with.programming.of.the.outputs.for.a.quiescent.condition:.
normally active
and.normally.not.
active..For.details.about.programming.the.operating.mode.of.the.control.outputs.and.the.choice.of.activation.events,.refer.to.the.section.on.“
set
> CONTrOL OUTPUT
”.(par..8.6.2).
•.
Status of outputs with the system in a quiescent condition (output contacts not activated)
•.
Status of outputs with the system in an active condition (output contacts activated)
relè A
relè B
relè F
relay A
OUT.1
Normal.state.OFF
OUT.2
Normal.state.ON...............
OUT.6
Normal.state.ON
RELAY.AUX.1
Normal.state.ON
RELAY.AUX.2
Normal.state.OFF
Examples.of.settings.of..
output.parameters.in:
set > CONTrOL OUTPUT
5.3.1
Local output contacts for a 12-zone system
The.two.PA8506-V.units,.connected.to.one.another.so.as.to.form.a.12-zone.system,.will.activate.their.output.contacts.depending.on.the.individual.
status.of.each.PA8506-V.unit,.regardless.of.that.of.the.other.unit..The.output.contacts.(CONTROL.OUTPUTS).from.OUT1.to.OUT6.of.one.PA8506-
V.unit.cannot.be.connected.to.the.output.contacts.of.a.second.PA8506-V.unit..The.RELAY.1.and.RELAY.2.output.contacts.of.one.PA8506-V.unit.
can.be.connected.to.the.RELAY.1.and.RELAY.2.contacts.of.another.PA8506-V.unit,.either.in.series.or.in.parallel,.so.as.to.group.their.activation..
To.programme.the.output.contacts.for.each.of.the.PA8506-V.units,.refer.to.the.heading.“set.>.CONTROL.OUTPUT”.(point.8.6.2).
relay B
relay F
External peripheral unit
External peripheral unit