EBL128 Operating Instructions V1.1.x
25
7.4
Access level 3A
When the door has been opened via the fire brigade key and the door
switch has been activated (LED "Door open" is lit),
the service /
maintenance personnel
have access like in access level 2A and 2B
and after access code for level 3A
25
the following menus:
H5 Service
A1 Disconnect / Re-connect COM loop
A2 Disconnect/Re-connect zone line input
A3 Calibration of supervised outputs
A4 Sensitive fault detection mode
A5 Service mode for COM-loop
A6 Show information about site specific data
A7 Display current consumption on COM loop
A8 Display statistics for COM loop
A9 Activate address setting mode for DU
H8 Maintenance
S1 Acknowledge SERVICE signal.
S2 Clear weekly average.
S3 Test alarm devices.
S4 Safe shut down of control unit.
S5 Activate address in alarm mode.
S6 Change access code for service and maintenance (access level
3A).
S7 Change access code for PC-communication.
7.5
Access level 3B
Used by Service / maintenance / commissioning engineers when a PC
(i.e.
Win128
) is to be connected to EBL128 for backup / download of
site specific data.
Connect the PC and logon to EBL128 from the PC (Win128).
25
If the code for access level 3A has already been used to logon to access
level 2B, a new logon is not required.