Panasonic Electric Works Nordic AB
MEW01091
Rev: 3
EBL128 Operating Instructions V1.1.x
108
NOTE!
After the calibration it is recommended to do a "Safe
shutdown of control unit" (see menu H8/S4). This will save the SSW
data (e.g. the calibration values) in a Flash ROM (see page 74).
28.4
Sensitive fault detection mode (H5/A4)
"Sensitive fault detection mode" means that the time delay is reduced
for all type of faults, which makes it possible find faults during the
commissioning instead of later.
NOTE!
Don't forget to turn this mode off after the commissioning.
Action
Text in display
Comments
"Access"
According to chapter
"Access code for service
and maintenance", see
page 104.
Disconnect / Re-connect COM loop
ACCEPT? A1
Scroll to menu A4
Sensitive fault detection mode
ACCEPT? A4
"A"
Sensitive fault detection mode: 0
(0 = off, 1 = on)
Press "A" or "1" and "A"
to accept. ON is indicated
by LED "Fault tx
activated" (L11) and the
"Fault" output for routing
equipment. This mode is
ON until turned OFF in
this menu (A4).
E.g. "1", "A"
Sensitive fault detection mode
ACCEPT? A4
Scroll or press "Return" to
H5. Scroll or press
"Return" to log off.
NOTE!
Don't forget to turn this mode off after the commissioning.