Panasonic Electric Works Nordic AB
MEW01091
Rev: 3
EBL128 Operating Instructions V1.1.x
84
25.3
Disable output (H2/B3)
Control outputs,
except outputs of type "alarm device"
, can be
individually disabled. Disabled output will stay in (or return to) the
normal condition for the output respectively.
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 78.
Scroll to menu H2.
Disable or re-enable
ACCEPT? H2
"A"
Disable zone
ACCEPT? B1
Scroll to menu B3.
Disable output
ACCEPT? B3
"A"
Disable output: Type: 0
0=Loop unit 1=S 2=R0 3=EXPB ACCEPT?
Press:
"
0
"=MIO (3361) or
ASI (3377) or
ASB (337
9
) or
AOU (3364)
"
1
"=C.i.e. output S0-S1
"
2
"=C.i.e. output R0
"
3
"=C.i.e. exp. board
output.
Press "A" to accept.
"A"
Depending on the
chosen type, 0, 1, 2 or 3
the following will be
shown:
Disable technical address 000 output 0
ACCEPT?
Disable S0
ACCEPT?
Disable R0
ACCEPT?
Disable expansion board 0 output 0
ACCEPT?
Regarding the ASI
(3377) & ASB (337
9
)
unit outputs:
0=high priority
1=low priority
Write the data.
Press "A" to accept.
LED "Disablements"
(L8) will light up.
"A"
Disable output: Type: 0
0=Loop unit 1=S 2=R0 3=EXPB ACCEPT?
If more disablements
shall be done, continue
like above. If not, press
"Return" to menu B3.
Scroll or press "Return"
to menu H2. Scroll or
press "Return" to log off.
80
Expansion board (EXPB) 0-7.
Relay output 0-7 (4581) alt. Output 0-2 (4583).