Panasonic Electric Works Nordic AB
MEW01091
Rev: 3
EBL128 Operating Instructions V1.1.x
88
25.7
Re-enable output (H2/B7)
Disabled outputs are listed in menu H4/U1.
When all outputs have been re-enabled, the LED "Disablements" (L8)
will be turned OFF, if there are no other disablements.
When all outputs type Alarm devices have been re-enabled, the LED
"
Fault / Disablements
Alarm devices" (L13) will be turned OFF.
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 78.
Scroll to menu H2.
Disable or re-enable
ACCEPT? H2
"A"
Disable zone
ACCEPT? B1
Scroll to menu B7.
Re-enable output
ACCEPT? B7
"A"
Re-enable output: 0
0=Loop unit 1=S 2=R0 3=EXPB ACCEPT?
Press:
"
0
"=MIO (3361) or
ASI (3377) or
ASB (3378) or
AOU (3364)
"
1
"=C.i.e. output S0-S1
"
2
"=C.i.e. output R0
"
3
"=C.i.e. exp. board
output.
Press "A" to accept.
"A"
Depending on the
chosen type, 0, 1, 2 or 3
the following will be
shown:
Re-enable technical address 000 output 0
ACCEPT? L
Re-enable S0
ACCEPT? L
Re-enable R0
ACCEPT? L
Re-enable expansion board 0 output 0
ACCEPT? L
If there are no outputs to
re-enable, menu B7 will be
shown again.
L=a list in which you can
scroll. Regarding the ASI
(3377) & ASB (3378) unit
outputs:
0=high priority
1=low priority
If it's the correct output to
re-enable, press "A" to
accept. If not, scroll or
write the wanted output
and press "A" to accept.
81
Expansion board (EXPB) 0-7.
Relay output 0-7 (4581) alt. Output 0-2 (4583).