EBL128 Operating Instructions V1.1.x
17
LED indicators on the Control Panel (CP)
LED indicator
Indicating
L7
General fault (yellow)
Fault(s), i.e. not acknowledged fault(s) and/or
acknowledged but not corrected fault(s).
L8
Disablements (yellow)
Something is disabled / disconnected via a menu or
automatically via "Single encapsulated reset"
7
.
L9
Test mode (yellow)
One or more zones are in "test mode".
L10
Door open (yellow)
A door is open (in EBL128 or an ext. FBP).
11
12
Störung Löschanlage
(yellow)
An input with trigger condition "Extinguishing system
fault" is activated (true).
L11
Fault tx activated (yellow)
Output activated for Fault tx (routing equipment), i.e.
one or more not acknowledged faults.
Test of routing equipment in progress (see menu H1).
L12
Service (yellow)
One or more sensors have reached the service level.
See menu H4/U6.
12
Leitungsstörung
Löschanlage (yellow)
Short-circuit or cut-off (open circuit) on a supervised
input OR a supervised output type "Extinguishing".
L13
Fault / Disablements
Alarm devices (yellow)
One or more outputs (type Alarm device) are disabled.
Blinking
: One or more supervised outputs (type
Alarm device) have generated fault(s).
13
L14
System fault (yellow)
EBL128 is not running (because of S/W, CPU or
memory fault).
14
L15
Fault / Disablements
Fire brigade tx (yellow)
Output for Fire brigade tx (routing equipment) is
disabled via menu (H2/B3) or via an open door.
11
Blinking
: Routing equipment power supply output
15
or one or more supervised outputs (type Routing
equipment) have generated fault(s).
16
11
See also chapter "Door open", page 36.
12
L10 and L12 have different functions on the German front.
13
This is also valid when EBL128 has no "contact" with a unit with such an
output, e.g. a 3377, 3378, 3361, etc.
14
The LED is turned on during restart and stays on for restart code other
than 00 and 03 until the fault is acknowledged.
15
Main board terminal block "J1:11-12".
16
This is also valid when EBL128 has no "contact" with a unit with such an
output, e.g. an I/O unit 3361, etc.