EPU=1728 (Ext. Presentation Unit)
There is no SSD (Site Specific Data) downloaded to the unit or
something is wrong in the downloaded SSD.
FAULT: Site specific data (SSD), FBP x
FBP
=1826 / 1828 (Ext. Fire Brigade Panel)
There is no SSD (Site Specific Data) downloaded to the unit or
something is wrong in the downloaded SSD.
FAULT: Wrong type, expansion board x
Valid for the 8 zones exp. board 4580, the 8 relays exp. board 4581
and the Inputs and outputs exp. board 4583 mounted in the c.i.e.
(EBL128). Also valid for the I/O Matrix board 4582 connected on the
COM loop, i.e. mounted outside the c.i.e.
The board is not the same type as programmed in the SSD. Change
the programming (via Win128)
or
the board.
FAULT: Wrong type of unit xx-xx
Press "
" to see the technical address.
FAULT: Wrong type of unit t.addr xxx
The unit is not the same type as programmed in the SSD. Change the
programming (via Win128)
or
the unit.
FAULT: Zone line input xx-xx
Press "
" to see the technical address or the expansion board (4580)
number and input number.
FAULT: Zone line input t.addr xxx
FAULT: Zone line input x exp board x
a.
Valid for the Multi purpose I/O unit 3361, connected on the COM
loop, monitored zone line input Z: Break on the zone line or wrong /
no end-of-line capacitor / short-circuit (if not programmed for fire
alarm at short-circuit).
b.
Valid for the 8 zones exp. board 4580, mounted in the c.i.e.
(EBL128): Break on the zone line, wrong / no end-of-line capacitor /
short-circuit (if not programmed for fire alarm at short-circuit). .