EBL128 Operating Instructions V1.1.x
45
001 ZONE-ADDR 12-45 LAST ZONE 12 No. 01
Re-enable zone: ZZ ACCEPT?
This is a list of disabled zones. Scroll to or write the wanted zone
number and press "A". If more zones are to be re-enabled, repeat the
procedure.
16.2.1.7
Re-enable zone / address (X7)
001 ZONE-ADDR 12-45 LAST ZONE 12 No. 01
Re-enable zone / address ACCEPT? X7
Press "A". E.g.:
001 ZONE-ADDR 12-45 LAST ZONE 12 No. 01
Re-enable zone: ZZ Address: 00 ACCEPT?
This is a list of disabled zone-addresses. Scroll to or write the wanted
zone-address and press "A". If more zone-addresses are to be re-
enabled, repeat the procedure.
16.2.1.8
Disable / Re-enable control (X8)
001 ZONE-ADDR 12-45 LAST ZONE 12 No. 01
Disable/Re-enable control ACCEPT? X8
Press "A". E.g.:
001 ZONE-ADDR 12-45 LAST ZONE 12 No. 01
Dis(=0) or re-en(=1) control? 1 ACCEPT?
To disable, press "0" and "A". (To re-enable, press "1" and "A".). For
more information, see chapter "Disable all control, extinguishing,
ventilation and alarm device outputs (H2/B4), page 85.
16.2.1.9
Disable / Re-enable alarm devices (X9)
001 ZONE-ADDR 12-45 LAST ZONE 12 No. 01
Disable/Re-enable alarm dev. ACCEPT? X9
Press "A". E.g.:
001 ZONE-ADDR 12-45 LAST ZONE 12 No. 01
Dis(=0) or re-en(=1) alarm dev?1 ACCEPT?
To disable, press "0" and "A". (To re-enable, press "1" and "A".). For
more information, see chapter "Re-enable all control, extinguishing,
ventilation or alarm device outputs (H2/B8), page 90.
16.2.2
Alert Annunciation alarm (AA alarm)
Indications, actions etc. as for a normal fire alarm
except that
EBL128 output for routing equipment (Fire brigade tx) will not be
activated directly.
An
AA
alarm is indicated by the LED "Fire
brigade tx delay" (L16). The
AA
alarm has to be acknowledged
within an acknowledge time and reset within and an investigation