EBL128 Operating Instructions V1.1.x
62
EBL128 cannotcommunicate with the board. Check / edit the address.
Check the cables / connections.
FAULT: No reply FBP x
FBP=1826 / 1828. (Ext. Fire Brigade Panel)
EBL128 cannotcommunicate with the unit. Check / edit the address
and the S/W mode in the unit (or edit the SSD).
FAULT: Output Sx
This is valid for the EBL128 supervised voltage outputs S0 and S1.
If the output is programmed for sounders (type Alarm devices), it is
also indicated by LED "
Fault / Disablements
Alarm devices" (L13)
blinking.
If the output is programmed for a fire brigade tx (type Routing
equipment), it is also indicated by LED "
Fault / Disablements
Fire
brigade tx" (L15) blinking.
Calibration not performed via menu H5/A3.
Short-circuit / break on the connected cable / equipment.
Blown fuse "F8" (S0) or "F6" (S1) on the main board 4556.
Connected equipment might be "missing".
End-of-line resistor(s) missing or not correct value (see
drawing 128-22). 1- 5 resistors 33K.
NOTE!
The calibrated value has to be in the range 4K7-50K.
FAULT: Output x expansion board x
A fault on the supervised output x on the expansion board (4583) with
address x.
If the output is programmed for sounders (type Alarm devices), it is
also indicated by LED "
Fault / Disablements
Alarm devices" (L13)
blinking.
If the output is programmed for fire brigade tx (type Routing
equipment), it is also indicated by LED "
Fault / Disablements
Fire
brigade tx" (L15) blinking.
Calibration not performed via menu H5/A3.
Short-circuit / break on the connected cable / equipment.
Blown fuse "F1" (Output 0) or "F2" (Output 1) on the 4583
board.
Connected equipment might be missing.
End-of-line resistor(s) missing or not correct value (1-5 x
33K).
NOTE!
The calibrated value has to be in the range 4K7-50K.