This Supplement has been created to introduce new addressable devices and a new FACP software
feature which allows the control panel to monitor and printout the sensitivity for each addressable
smoke detector connected to the system.

I. Addressable Devices

Legacy Addressable Devices

The legacy 300 Series addressable devices, which continue to be compatible with all versions of the addressable FACP (Fire
Alarm Control Panel), have been discontinued and can no longer be ordered.  These devices include the following:

•   SD300 - Photoelectric Smoke Detector
•   SD300T - Photoelectric Smoke Detector with Thermal Sensor
•   CP300 - Ionization Smoke Detector
•   M300 - Monitor Module
•   M301 - Miniature Monitor Module
•   M302 - two-wire Monitor Module
•   C302 - Control/Relay Module

New Addressable Devices

The newer addressable devices, which are compatible with all versions of the FACP, incorporate the latest technology.  Each
addressable device can be set to an address ranging between 001 and 099.  

Do not set the address rotary switches to a value

higher than 099 since it will not be recognized by the FACP.

  A blinking LED on each detector and monitor module indicates

communication between the device and the control panel.  Legacy and new addressable devices can be mixed on the same SLC
loop.

The new devices include the following:

•   SD350: an intelligent, addressable low profile photoelectric smoke detector which provides smoke sensing technology
•   SD350T: an intelligent, addressable low profile photoelectric smoke detector which provides smoke sensing technology

and a 135

o

 fixed thermal sensor

•   CP350: an intelligent, addressable low profile ionization smoke detector which measures the level of combustion

products in its chamber using the 'ionization' principle

•   D350P: an intelligent, addressable photoelectric duct smoke detector.
•   D350RP: an intelligent, addressable photoelectric duct smoke detector with a built-in alarm relay
•   MMF-300: an addressable monitor module for monitoring normally open contact alarm initiating devices, such as

manual pull stations, four-wire smoke detectors, heat detectors, waterflow, security contacts and supervisory devices.
Circuits can be connected Style B (Class B) or Style D (Class A)

•   MDF-300: an addressable dual monitor module which functions the same as the MMF-300 except circuits can only be

connected as Style B (Class B)

•   MMF-301: an addressable monitor module that is functionally similar to an MMF-300 but offered in a smaller package

for mounting directly in the electrical box of the device being monitored.  Circuits can only be connected as Style B
(Class B)

•   MMF-302: an addressable monitor module used primarily for two-wire smoke detectors in addition to normally open

contact devices.  Circuits can be connected Style B (Class B) or Style D (Class A)

•   CMF-300: an addressable control module used to connect NACs (Notification Appliance Circuits) to power and

supervise compatible, UL-listed notification appliances.  The circuits can be wired as Style Y (Class B) or Style Z
(Class A)

•   CRF-300: an addressable control relay module which is functionally similar to the CMF-300 but used as a Form-C relay

module

New Addressable Devices &

Detector Sensitivity

Supplement

Document 51526   Rev A  02/14/01  ECN 01-080