20
SSD programming & download
The
S
ite
S
pecific
D
ata (SSD) for an installation is created
(programmed) via the PC program
Win128
, which also is used to
download the SSD into the EBL128 c.i.e. and/or 1728, 1735 / 1736 &
1826 / 1828 units. The SSD will be saved in a file named
xxxxx.Win128
.
65
20.1
SSD programming
The SSD programming can be made "in your office" and afterwards
be downloaded to EBL128 on site.
20.2
Auto generating SSD
If you are on site, the
Auto generate
function can be used to create
the SSD. Open a new installation in Win128, connect the PC to the
RS232 connector J3 in EBL128 (on the main board) and log on.
66
In
"Tools" menu select "Auto generate…". The COM loop units
67
and
the FBP/AAU units connected to EBL128, will now be identified and
listed in Win128, i.e. the SSD will be auto generated with default
settings for all units. Save the installation (SSD). The SSD can be
downloaded (see below) to EBL128 directly or be edited before the
download.
20.3
SSD download
The PC with Win128 has to be connected to the RS232 connector J3
in EBL128 (on the main board). Open the wanted installation
(xxxxx.Win128) and log on to EBL128.
66
In "Tools" menu select
"Download SSD…" to open the dialog box.
Mark the required checkbox(es). Click "Start download".
Information will be shown in the dialog box (progress bar) and in the
display in EBL128:
65
xxxxx
= A suitable name of the installation.
66
Access code for level 4 shall be entered via the PC (i.e. via Win128).
67
Each unit have to be running i.e. be connected, power supplied and the
address, mode etc. have to be set.
NOTE!
During this check the COM loop
will be disconnected (disabled) and no alarms or faults can be activated.
Disconnected COM loop is indicated by the LED "Disablements" (L8).