EBL128 Operating Instructions V1.1.x
85
25.4
Disable all control, extinguishing, venti-
lation and alarm device outputs (H2/B4)
Outputs programmed as type Control (general), type Fire ventilation,
type Extinguishing system and type Alarm devices can for the type
respectively be disabled all at the same time.
Disabled output
means
that even if the control expression (trigger condition) for the output
respectively is fulfilled (true), the output will not be activated.
Disabled outputs are shown in menu H4/U1.
The outputs will be disabled until re-enabled again
(via H2/B8).
NOTE!
This function for alarm devices is
not
the same as for push
button "Silence alarm devices" (P3), see chapter "Silence Alarm
devices", page 27. This function has higher priority than "Silence
alarm devices".
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 78.
Scroll to menu H2.
Disable or re-enable
ACCEPT? H2
"A"
Disable zone
ACCEPT? B1
Scroll to menu B4.
Disable all control,
ventilation, exting
or alarm device outputs ACCEPT? B4
"A"
Disable type:
0 0=Control 1=Ventilation
2=Exting 3=Alarm devices
ACCEPT?
Press:
"
0
"=control output
"
1
"=
ventilation
output
"
2
"=
extinguishing
output
"
3
"=alarm device output.
Press "A" to accept.
LED "Disablements" (L8)
will light up.
If type 3 = alarm devices
are disabled also the LED
"
Fault / Disablements
Alarm devices" (L13) will
light up.
Press 0, 1, 2 or 3
"A"
Disable all control,
ventilation, exting
or alarm device outputs ACCEPT? B4
Scroll or press "Return" to
menu H2. Scroll or press
"Return" to log off.
"Return"
Disable or re-enable
ACCEPT? H2